beautypg.com

LST IBSST-DR-P01 User Manual

LST Safety

background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

IBSST-DR-P0x_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

• ADM loop technology with

System Sensor/200 protocol

• Can be activated with two different

tone types, 32 tone types selectable

• Sound level selectable in three steps

– up to 95dB(A)

• Low power consumption
• Versions with or without integrated

dual-isolator available

• Two base types available – IP24, IP44

Specifi cations

Operating voltage

Supply through loop voltage

Sound level (detector installed)

typ. 70dB(A) at 1m distance (low)

typ. 79dB(A) at 1m distance (medium)

typ. 87dB(A) at 1m distance (high)

max. 95dB(A) at 1m distance (high)

Flash frequency

1Hz

Ambient temperature

-25°C to +70°C

Dimensions ш Ч H

112 × 42 (mm) (without detector, incl. base LPBW)

Weight

136g

Colour

red / cream, RAL 9001

The loop powered sounder with strobe is fi tted into a

round, red plastic case. It is powered and actuated as

a module via the ADM loop with System Sensor/200

protocol. Fire Detectors Series 200 can be fi tted into

the integrated base.

The sounder can be activated by a Fire Detection Con-

trol Panel Series BC216 with two different tone types,

depending on the parameter setup. One of 32 different

tone type combinations can be selected with a DIL-

switch. The following tones are available, for example:

• Continuous tone 660Hz,

• Emergency signal according to DIN 33404,

• Slow whoop tone according to NEN 2575,

• Alternating tone 800/970Hz, and many more.

The sound level can be selected in 3 steps. The stro-

be is always activated together with the sounder. The

address of the sounder/strobe is selected with two

decadic rotary switches located at the bottom of the

device.

The device is designed for indoor surface mounting.

For this purpose a special base is needed. Two diffe-

rent base types for protection classes IP24 or IP44

are available, depending on the application. An optional

mounting plate can be supplied for surface mounted

cabling.

The sounder/strobe is available in two different versi-

ons: With or without integrated dual-isolator module.

This manual is related to the following products: