beautypg.com

LST ECO1005 User Manual

Description

background image

© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED

ECO1005_DBL_LST_EN_0804.PDF • PAGE 1

A

Building Safety. Building Security.

Description

The Thermal ROR Detector ECO1005 reacts to tem-

perature changes within defi ned periods of time, up

to a maximum temperature of 58°C. The intelligent

evaluation of these data allows the early detection of

spreading fi res.

Addressable conventional technology is used for alarm

transmission to the fi re detection control panel. By

means of the Address Module NG58-1, each detector

can be addressed individually.

A test activation of the detector can be carried out

using the Remote Test Unit ECO1000RTU. The detec-

tor can be attached to various detector bases and it

can be protected against theft.

• Addressable conventional technology
• Maximum temperature 58°C
• Individual detector addressing by

means of optional address module

• Optional connection of remote

indicator

• Function testable with Remote Test

Unit ECO1000RTU

Specifi cations

Operating voltage

Supply through the detector line voltage

Current consumption

typ. 75µA (quiescent)

Alarm temperature

58°C (maximum-heat component)

Operating temperature

max. +45°C

Ambient temperature

-30°C to +70°C

Relative humidity

5 – 95% (no condensation)

Dimensions ш Ч H

102 × 40.5 (mm)

Colour

white

Weight

70g

Approval

VdS G201016

Order number

242045

Order name