LST 5451EIS User Manual
Description
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
5451EIS_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
The Intrinsically Safe Thermal ROR Detector 5451EIS
uses the rate-of-rise heat detection principle and was
developed for the fi re detection in hazardous areas.
The detector, which is a combined maximum/rate-of-
rise heat detector, is assigned to class A1R and can be
used up to a maximum room height of 7.5m.
Conventional technology is used for alarm transmission
to the fi re detection control panel. In conjunction with
the Safety Barrier ES58-2, the detector reaches the
given Ex classifi cation. The two LEDs with 360° visibility
indicate the activated condition of the detector.
A detector function test can be conveniently conducted
using a magnet or a detector test device. The detector
can be attached to various bases and it can be protec-
ted against theft.
• Conventional technology
• Maximum temperature 60°C
• Up to 20 detectors can be connected
to one safety barrier
• Function testable with magnet
• ATEX certifi ed
Specifi cations
Ignition protection
intrinsically safe
Ex classifi cation
EEx ia IIB T5
Current consumption
typ. 100µA (quiescent)
Alarm temperature
60°C (maximum-heat component)
Ambient temperature
-10°C to +43°C (continuous operation)
Relative humidity
10 – 93% (no condensation)
Dimensions ш Ч H
104 × 54 (mm)
Colour
cream
Weight
80g
Approval
BASEEFA03ATEX0155X
VdS G296050
Order number
242015
Order name
IS Thermal ROR Detector/Conv./400/SS 5451EIS