Description

With the Detector Zone Extension MGE8-1 the fi re de-

tection control panel Series BC016 can be extended

from 8 to 16 addressable detector zones. Up to 64

detectors (addresses) per detector line can be indivi-

dually identifi ed with the aid of an address module. In

the event of an alarm, the fi re detection control panel

indicates the number of the detector that triggers the

alarm fi rst.

Depending on the type of detector (manual call point,

automatic fi re detector with or without alarm verifi cati-

on, fault message contacts as well as contacts for tech-

nical messages), the function of the detector zone can

be set separately for each detector line. Each input of

the Detector Zone Extension is protected against over-

voltage and thus provides high system stability.

• Extends fi re detection control panels

Series BC016 to 16 detector lines in

addressable conventional technology

• Individual detector addressing with

optional address module

• Individual setting of detector zone

function

• Lines monitored for wire breakage,

short circuit, and short to earth

Specifi cations

Current consumption at 24V

typ. 32mA (8 zones terminated, without detectors)

Line voltage

typ. 20.0V

Line current

typ. 3.8mA

End-of-line resistance

5.6kΩ or 3,3kΩ (depending on setup)

Line resistance

max. 50Ω per core

Ambient temperature

-5°C to +50°C

Dimensions L × W × H

100 Ч 65 Ч 15 (mm)

Weight

80g

Part No.

210110

Order name

Detector Zone Extension MGE8-1