LST ECO1000BREL24L User Manual
Description specifi cations
© LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX +43 1 52114-27
[email protected] • WWW.LST.AT • ALL RIGHTS RESERVED
ECO1000BREL24L_DBL_LST_EN_0804.PDF • PAGE 1
A
Building Safety. Building Security.
Description
Specifi cations
The Detector Relay Base ECO1000BREL24L with inte-
grated relay output is designed for the easy connection
of automatic detectors Series ECO1000. Due to its ro-
bust multi-wire screw terminals, the detectors can be
wired with ease, thus achieving a secure and durable
connection.
The relay output is activated through the alarm activati-
on of the inserted detector and remains active until the
alarm is reset on the fi re detection control panel. The
application has to comply with the guidelines in the LST
Connection of Detectors.
During construction work (or when the detector has
been removed) the detector line can be connected
through via an auxiliary contact, which is integrated
into the base. With that, the whole wiring of the detec-
tor line can be examined without risking contamination
of the detectors. The contact is automatically opened
by installing the detector.
The base is designed for surface mounting in dry
rooms. A mechanical theft protection of the detector
can optionally be activated at the detector base.
• Suitable for automatic detectors in
conventional technology
• Relay output with dry change-over
contact
• Screw terminals for secure
connection of multiple wires
• Test contact for examining the
detector line without detectors
• Mechanical theft protection can be
activated
Operating voltage
Supply through the detector line voltage
Current consumption
1µA (quiescent), 30mA (active)
Contact rating
1A at 30VDC
Ambient temperature
-30°C to +70°C
Relative humidity
5 – 93% (no condensation)
Dimensions ш Ч H
102.5 × 33 (mm)
Colour
white
Weight
70g
Order number
246141
Order name
Detector Relay Base/Conv./1000/SS ECO1000BREL24L