beautypg.com

Liebert STS2 User Manual

Page 94

background image

Alarms and Faults

86

81

SOURCES OUT OF SYNC

Source 1 and Source 2 are out of synchronization.

A, E

82

LOAD ON ALT SOURCE

The output load is running on the alternate source.

A, E

83

AUTO REXFER INHIBIT

Automatic retransfer is inhibited.

A, E

84

CB1 (S1) OPEN

Source 1, Circuit Breaker 1 is open.

A, E

85

CB2 (S2) OPEN

Source 2, Circuit Breaker 2 is open.

A, E

86

CB4 (S1 BYP) CLOSED

Source 1 on bypass, Circuit Breaker 4 is closed.

A, E

87

CB5 (S2 BYP) CLOSED

Source 2 on bypass, Circuit Breaker 5 is closed.

A, E

88

CB3 (OUTPUT) OPEN

Output circuit breaker (CB3) is open.

A, E

89

CB3A (OUTPUT) OPEN

Output circuit breaker (CB3A) is open.

A, E

90

S1 PHASE ROT ERROR

Source 1 phase rotation error.

A, E

91

S2 PHASE ROT ERROR

Source 2 phase rotation error.

A, E

92

TRANSFER INHIBITED

Transfer inhibited.

A, E

93

OUTPUT UV

Output is under voltage.

D, F, A, E

94

HISTORY LOG FULL

Both History Logs have been written and no more history logs can be

written without clearing one of the logs

A, E

96

INPUT 1 OV INPUT

Source 1 over voltage

A, E

97

INPUT 1 UV INPUT

Source 1 under voltage

A, E

98

INPUT 2 OV INPUT

Source 2 over voltage

A, E

99

INPUT 2 UV INPUT

Source 2 under voltage

A, E

100

LOAD OVERCURRENT

Output over current

A, E

101

GROUND OVERCURRENT

Ground over current

A, E

102

NEUTRAL OVERCURRENT

Neutral over curremt

A, E

103

LOAD VOLTAGE THD

Voltage THD has exceeded the set limit

A, E

104

INPUT 1 CB6 OPEN

Source 1 input Circuit Breaker 6 is open

A, E

105

INPUT 2 CB7 OPEN

Source 2 Input Circuit Breaker 7 is open

A, E

106

INPUT 1 OF/UF

Source 1 over frequency/under frequency

A, E

107

INPUT 2 OF/UF

Source 2 over frequency/under frequency

A, E

120

121

122

123

124

125

126

127

INPUT CONTACT #1

INPUT CONTACT #2

INPUT CONTACT #3

INPUT CONTACT #4

INPUT CONTACT #5

INPUT CONTACT #6

INPUT CONTACT #7

INPUT CONTACT #8

Input Contact # x is an optional alarm input. The alarm name can be

programmed with an alarm name from the Input Contactor Isolator

settings option under the Comm Options. See Configuring the Input

Contact Isolator Settings on page 108. The alarm is sent to Monitor

DSP. The LCD logs the alarm with the programmed name. Monitor

DSP logs it with the generic name which is how it is reported to the

SVT query.

A, E

128

CONFIG MODIFIED

A setpoint configuration has changed.

E

129

PASSWORD CHANGED

The password for touch screen access has been modified and saved.

E

130

TIME REPROGRAMMED

The system’s time has been reset and saved.

E

131

DATE REPROGRAMMED

The system’s date has been reset and saved.

E

132

EVENT LOG CLEARED

The event log has been erased.

E

133

HIST LOGS CLEARED

Both History Logs have been erased.

E

134

XFER COUNT CLEARED

Transfer counter reset to 0

E

135

KWH COUNT CLEARED

KW-Hrs counter reset to 0

E

Table 12

Event messages (continued)

ID

Alarm Message

Description/Cause

Action

This manual is related to the following products: