Table 4 input/output conduit plate specifications, Figure 5, Circuit breakers10 – Liebert STS2 User Manual
Page 18: Figure 6, Breakers, Table 4, Input/output conduit plate specifications, H 6 for ty
![background image](/manuals/163511/18/background.png)
Power and Control Wiring
10
Figure 5
Typical STS2/PDU, one-line diagram, with inline distribution, dual static switch output circuit
breakers
Figure 6
Typical STS2/PDU, one-line diagram, with I-Line distribution, dual static switch output circuit
breakers
The input and output power wire size should be based on the overcurrent protection device, observing
the NEC and local codes.
The STS2/PDU output power, ground and neutral busbars accommodate a wide range of wire sizes.
The STS2/PDU busbars accommodate standard two-hole lugs.
Table 4
Input/output conduit plate specifications
Rating
Maximum Number
of Conduits
Size, in.
250A
12
2"
8
2-1/2"
6
3" or 3-1/2"
400-600A
6
2"
4
2-1/2" or 3"
800A
6
2-1/2"
5
3" or 3-1/2"