Liebert STS2 User Manual
Page 132
Event Message Help Text
124
PWR SPLY S2 AC FAIL
Power Supply Source 2 AC Failed
The AC input power to the power supplies from Source 2 has failed.
The power supplies are now operating on AC power from Source 1. The AC input from Source 2 is still good.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contigu-
ous United States contact Liebert Global Services, if available in your area. For international areas not covered
by Liebert Global Services, the Liebert authorized distributor can provide technical support.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.
PWR SPLY LOGIC FAIL
Power Supply Module Failed
The power supply logic module contained in the primary power supply has failed.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contigu-
ous United States contact Liebert Global Services, if available in your area. For international areas not covered
by Liebert Global Services, the Liebert authorized distributor can provide technical support.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
This event was written to the Event Log, is so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.
OUT VOLT SENSE FAIL
Output Voltage Sense Module Failed
The module contained on the snubber monitoring the output voltage has failed.
Press SILENCE on the touch screen to turn off the audible alarm, if so configured. If you are accessing the
STS2/PDU system from a terminal, type SH and press RETURN on your keyboard to turn off the audible
alarm.
Contact technical support; in the United States, call 1-800-LIEBERT (1-800-543-2378). Outside the 48 contigu-
ous United States contact Liebert Global Services, if available in your area. For international areas not covered
by Liebert Global Services, the Liebert authorized distributor can provide technical support.
This event was written to the Event Log, if so configured.
The alarm has triggered a message to be sent to the modem, if so configured.
If configured to be a latching alarm, press RESET on the display. If you are accessing the unit from a terminal,
type CA and press RETURN on your keyboard.