2 shutdown in maintenance bypass mode, Shutdown in maintenance bypass mode – Liebert STS2 User Manual
Page 89

Operating Instructions
81
10.5.2 Shutdown in Maintenance Bypass Mode
When the Static Transfer Switch 2 Power Distribution Unit is operating on bypass:
1. Turn off the load equipment per manufacturer’s recommendations.
2. Open CB8 or panelboard breakers and main if supplied
3. Open the bypass switch (CB4 or CB5) to turn off the static transfer switch output.
4. To completely de-energize the unit, turn open CB6 and CB7.
This manual is related to the following products:
See also other documents in the category Liebert Tools:
- PS250-50S (12 pages)
- SGH STEAM SL-14050 (16 pages)
- Ship-Ahead Input/Output Cabinet NXL (20 pages)
- NfinityTM (44 pages)
- 4000 (59 pages)
- 230V (40 pages)
- PSP (32 pages)
- UPStation GXT (20 pages)
- UPSTATION GXT 2U (38 pages)
- UPS Systems PSI XR (32 pages)
- 600TTM (91 pages)
- Series 600T (128 pages)
- GXT2 - 3X1 (42 pages)
- Nfinity (44 pages)
- PowerSure PSA 350VA to 1000VA (8 pages)
- 2U (16 pages)
- GXT2-6000 RT208 (52 pages)
- PowerSure Personal (12 pages)
- 2700VA (40 pages)
- Series 610 (44 pages)
- Emerson NX UPS System (88 pages)
- GXT 2U (44 pages)
- UPStation S VM12000 (38 pages)
- 1000kVA (120 pages)
- Nfinity 208 V / 240 V 60Hz (45 pages)
- UPS (28 pages)
- UPS System (121 pages)
- PowerSure PSI 1000 - 3000VA 60 Hz 120V (36 pages)
- GXT2-4500RT230 (40 pages)
- GXT2-6000RTL630 (44 pages)
- IntelliRack (2 pages)
- PowerSure PSA 350-1000VA (2 pages)
- 350-700 VA (11 pages)
- 500-650 VA (24 pages)
- PowerSure PS250-60S (13 pages)
- 130 kVA (102 pages)
- 30-130kVA (112 pages)
- GXT (23 pages)
- PSITM (34 pages)
- 600T (73 pages)
- 600T (88 pages)
- 610 (104 pages)
- GXTTM (30 pages)
- 700-3000 VA (30 pages)