0 options, 1 programmable relay board, Table 8 programmable relay board pinout – Liebert STS2 User Manual
Page 22: 2 input contact isolator board, Ptions, Programmable relay board, Input contact isolator board, Table 8, Programmable relay board pinout, 0 - options for de
Options
14
6.0
O
PTIONS
This section discusses the options available for the STS2/PDU. The communications options are also
discussed in 12.0 - Communication Interfaces.
6.1
Programmable Relay Board
The programmable relay board (PRB) provides a means to trigger an external device when an event
occurs in the STS2/PDU. Each PRB has 8 channels. Each channel has two sets of Form-C dry con-
tacts, rated 1A @ 30VDC or 250mA @ 125VAC.
Any alarm or event may be programmed to any channel or channels. Up to ten (10) events may be
programmed to a relay. If multiple events are grouped to one relay, group the events logically to sim-
plify troubleshooting when an event is triggered. The same alarm or event may be programmed to
more than one channel. Up to two programmable relay boards can be installed in the STS2/PDU for a
total of 16 channels. Programming is performed through the touch screen display.
See Configuring the Programmable Relay Board Settings on page 109 for default settings and
instructions for reconfiguring the relays. See Figures 47 and 48 for the location of the PRB. See
Figure 50 for wiring details. Table 8 provides the PRB pinout.
6.2
Input Contact Isolator Board
The Input Contact Isolator Board (ICI) provides an STS2/PDU module interface for up to eight exter-
nal user alarm or message inputs to be routed through the Static Transfer Switch 2 Power Distribu-
tion Unit’s alarm network. The eight contacts are normally open dry contacts. When a contact closes,
an event is triggered.
The Input Contact Isolator options are configured through the Input Contact Isolator dialog box,
which is accessed from the Comm Option dialog box on the touch screen display. You also can pro-
gram the alarm messages through this dialog box. See Configuring the Input Contact Isolator
Settings on page 108 for instructions on configuring the connections.
See Figures 47 and 48 for the location of the ICI. See Figure 51 for wiring details.
!
WARNING
All options must be installed by Liebert Global Services or Liebert factory-authorized service
provided by a Liebert distributor. The option area and customer control cable area contain
hazardous voltages if any of the input sources are on, even when the unit is in bypass. Turn
OFF all power sources before installing customer control cables to any option.
Table 8
Programmable relay board pinout
Channel
Pin No.
C
N.C.
N.O.
TB1
CH1
A
1-3
1
2
3
B
4-6
4
5
6
CH2
A
7-9
7
8
9
B
10-12
10
11
12
CH3
A
13-15
13
14
15
TB2
B
1-3
1
2
3
CH4
A
4-6
4
5
6
B
7-9
7
8
9
CH5
A
10-12
10
11
12
B
13-15
13
14
15
TB3
CH6
A
1-3
1
2
3
B
4-6
4
5
6
CH7
A
7-9
7
8
9
B
10-12
10
11
12
CH8
A
13-15
13
14
15
TB4
B
1-3
1
2
3
Key: N.O. = Normally Open; N/C. = Normally Closed; C = Common
Note: Pin 16 not used on TB1, TB2 and TB3.