beautypg.com

Installation and service manual – Lochinvar 399 User Manual

Page 63

background image

Installation and

Service Manual

63

Step 1

Does the power
switch provide
power to the

control panel?

Check the switch and/or
the line voltage.

Step 1

Does the power
switch provide
power to the

Check the switch and/or
the line voltage.

NO

YES

Combustion air
blowers come on.

NO

Is there 24VAC at B2 on
the terminal strip.

Check 24VAC at TH
(orange wire) on ignition
module(s).

Check all safety limit
devices and voltage from
the transformer to B2.

NO

Does F2 on ignition module
have 120VAC?

YES

YES

NO

Exchange ignition
module.

Check fan relay
board. Is there
120VAC on red
wires, pins #7 &

#9?

NO

YES

Is there continuity from the fan
relay board to fan(s)?

Replace fan
relay board.

Replace fan.

YES

Status light(s) does
not blink 1 flash
continuous.

Check air pressure
switch 24VAC on tan
wire (N.O.)

NO

24VAC at PS (tan wire) at ignition module
and/or connector plug for proving relay secure.

NO

YES

Check air pressure
switch for correct
pressures.

YES

Replace air pressure
switch.

NO

Correct air settings
may have to clean
burners/heat
exchanger.

YES

Does
igniter(s)
proof?

NO

Check Amp draw for 3.1 amps or
greater.

NO

Is Air Switch
bouncing?

YES

Replace igniter if less than 2.75 amps.

YES

YES

Step 2

Step 3

Step 4

YES

YES

Check flow switch, all connectors
behind control panel and Tekmar
output pins #16 and/or #20.

NO

Do the gas valve(s)
open and getting
24VAC?

Is the flame sense
signal to the ignition
module 5uA dc or
greater?

NO

YES

Check inlet/manifold gas pressure
both static and dynamic. Check
down draft.

NO

Is 24VAC present at the main unit connector
(3x5 amp plug) red and/or red - black wire,
block position #01 and #02?

YES

Replace gas valve.

NO

Check voltage at fan relay
board. No Voltage at pins #10
(red) and/or #02 (red-orange)
check ignition module pin #05
(replace RLY2402 if no
voltage). No Voltage at pins
#08 (red-black) and/or #03
(red-white) check Tekmar
controller pins #17-18 (red-
black) and/or #21-22 (red-
white) input/output voltage.

YES

Unit is running.

NO

Call our Technical
Service Department
1-800-722-2101

Step 6

Step 5

TROUBLESHOOTING GUIDE

990,000 - 2,070,000 Btu/hr Models

This manual is related to the following products: