beautypg.com

Installation and service manual – Lochinvar 399 User Manual

Page 27

background image

Installation and

Service Manual

27

Combustion air supply must be free of contaminants (see
Combustion and Ventilation Air, page 8). To prevent
recirculation of the flue products into the combustion air inlet,
follow all instructions in this section.

Outdoor Vent/Air Inlet Location

Keep venting areas free of obstructions. Keep area clean and
free of combustible and flammable materials. Maintain a
minimum clearance of 3" (76mm) to combustible surfaces and
a minimum of 3" (76mm) clearance to the air inlet. To avoid a
blocked air inlet or blocked flue condition, keep the outdoor
cap air inlet, flue outlet and drain slot clear of snow, ice, leaves,
debris, etc.

Do not install outdoor models directly on the ground. You must
install the outdoor unit on a concrete, brick, block, or other
non-combustible pad.

Do not locate unit so that high winds can deflect off of adjacent
walls, buildings or shrubbery causing recirculation.
Recirculation of flue products may cause operational
problems, bad combustion or damage to controls. Locate unit
at least 3 feet (0.91m) from any wall or vertical surface to
prevent wind conditions from affecting performance.

Multiple unit outdoor installations require 48" (1.22m)
clearance between each vent cap. Locate outdoor cap at least
48" (1.22m) below and 48" (1.22m) horizontally from any
window, door, walkway or gravity air intake.

Locate unit at least 10 feet (3.05m) away from any forced air
inlet.

Locate unit at least 3 feet (0.91m) outside any overhang.

Clearances around outdoor installations can change with time.
Do not allow the growth of trees, shrubs or other plants to
obstruct the proper operation of the outdoor vent system.

Do not install in locations where rain from building runoff
drains will spill onto the unit.

Outdoor Vent Cap Kits

* These kits include an outdoor vent cap and gasket.

Flue gas condensate can freeze on exterior walls or on the vent
cap. Frozen condensate on the vent cap can result in a blocked
flue condition. Some discoloration to exterior building or unit
surfaces can be expected. Adjacent brick or masonry surfaces
should be protected with a rust resistant sheet metal plate.

The Outdoor Vent Cap Kit

The optional outdoor vent cap kit is available from the
appliance manufacturer. The outdoor cap part numbers are
listed by unit size. See TABLE–H for kit numbers.

Install the outdoor vent cap on the rear of the unit (see FIG. 27).
Complete installation instructions are included with the
outdoor vent cap kit.

FIG. 27 Outdoor Vent Cap Installed on Rear of Unit

Kit*

Kit*

Input

without

with

Btu/hr

Pump Cover

Pump Cover

399,999

ODK3748

ODK3052

500,000

ODK3748

ODK3052

650,000

ODK3749

ODK3053

750,000

ODK3749

ODK3053

990,000

ODK3036

ODK3049

1,260,000

ODK3064

ODK3065

1,440,000

ODK3037

ODK3050

1,800,000

ODK3038

ODK3051

2,070,000

ODK3038

ODK3051

TABLE-H

Outdoor Vent Cap Kits

ƽ

WARNING: Only install outdoor models

outdoors and only use the vent cap supplied by
the appliance manufacturer. Personal injury or
product damage may result if any other cap is
used or if an outdoor model is used indoors.
Properly install all covers, doors and jacket
panels to ensure proper operation and prevent
a hazardous condition.

This manual is related to the following products: