State GPG/GPV-540A User Manual

Page 23

background image

23

DANGEr

THiS wATEr HEATEr iS EQUiPPED wiTH AN ADJUSTABLE

THErMOSTAT TO CONTrOL wATEr TEMPErATUrE. HOT

wATEr TEMPErATUrES rEQUirED FOr AUTOMATiC

DiSHwASHEr AND LAUNDry USE CAN CAUSE SCALD BUrNS

rESULTiNG iN SEriOUS PErSONAL iNJUry AND/Or DEATH.

THE TEMPErATUrE AT wHiCH iNJUry OCCUrS VAriES wiTH

THE PErSON’S AGE AND TiME OF EXPOSUrE. THE SLOwEr

rESPONSE TiME OF CHiLDrEN, AGED Or DiSABLED PErSONS

iNCrEASES THE HAZArDS TO THEM. NEVEr ALLOw SMALL

CHiLDrEN TO USE A HOT wATEr TAP, Or TO DrAw THEir

OwN BATH wATEr. NEVEr LEAVE A CHiLD Or DiSABLED

PErSON UNATTENDED iN A BATHTUB Or SHOwEr.

THE wATEr HEATEr SHOULD BE LOCATED iN AN ArEA

wHErE THE GENErAL PUBLiC DOES NOT HAVE ACCESS

TO SET TEMPErATUrES.

SETTiNG THE wATEr HEATEr TEMPErATUrE AT 120°F

(49°C) wiLL rEDUCE THE riSk OF SCALDS. Some states or

provinces require settings at specific lower temperatures.

Below you will find listed the approximate time-to-burn relationship

for normal adult skin. Short repeated heating cycles caused by

small hot water uses can cause temperatures at the point of use

to exceed the thermostat setting by up to 20F°. If you experience

this type of use, you should consider using lower temperature

settings to reduce scald hazards.

Temperature

Time to Produce 2nd & 3rd

Setting

Degree Burns on Adult Skin

180°F (82°C)

Nearly instantaneous

170°F (77°C)

Nearly instantaneous

160°F (71°C)

About 1/2 second

150°F (66°C)

About 1-1/2 seconds

140°F (60°C)

Less than 5 seconds

130°F (54°C)

About 30 seconds

120°F (49°C)

More than 5 minutes

Valves for reducing point-of-use temperature by mixing cold and

hot water are available. Also available are inexpensive devices

that attach to faucets to limit hot water temperatures. Contact a

licensed plumber or the local plumbing authority.
The water temperature is controlled by a thermostat, fig. 2, which

has two sensing elements. One sensor is located near the top of

the tank and the other is near the center. The thermostat is set in

the lowest position before the heater leaves the factory.

The dial is adjustable and may be set for 120

0

(49°C)

to 180

0

F

(82°C) water temperature, but 120

0

F (49°C) is the recommended

starting point. It is suggested the dial be placed on the lowest

setting which produces an acceptable hot water supply. This will

always give the most energy efficient operation. The temperature

control has a 4F° fixed differential.

ADJUSTMENT PrOCEDUrE (initial Start-Up)

A minimum dynamic gas supply pressure of 8” w.c. for natural

gas is required before making any adjustment to the gas control

pressure regulator. Attempts to adjust the regulator during periods

of low gas supply pressure could result in overfiring of the heater

when the gas supply pressure returns to normal.

SEQUENCE OF OPErATiON

– Power on.

– Heater in standby mode.

– Thermostat calls for heat.

– Blower motor starts.

– Blower operation closes the normally open blower prover/

blocked outlet safety pressure switch.

– On proof of airflow, Honeywell S8680J flame control module

energized.

– 45 seconds prepurge cycle begins.

– Following prepurge cycle, the pilot gas valve is energized.

– At the same time, the electronic spark generator in the module

produces a high voltage spark pulse output.

– The voltage generates a spark at the ignitor that lights the

pilot.

– If the pilot does not light (or flame signal is less than 1 micro

A) within 15 seconds system locks out and must be reset by

turning burner switch “OFF” for a minimum of 1 minute. During

system lockout, blower still runs.

– When the pilot flame is established (flame is sensed by flame

rod), the main gas valve is energized.

– Main gas flows to main burner where it’s ignited by the pilot

flame. Now heater is in Heating Mode.

– During the Heating Mode:

If gas line pressure drops below the setting point, the flame

module is de-energized, gas valves closed, blower still runs.

If gas line pressure drops below the setting point then gas line

pressure increases to above the setpoint, heater starts again

from purging cycle.

If gas line pressure fluctuates around the setpoint too quick

(less than a second) burner may still run with excessive gas

valve ON/OFF cycle you must turn off the unit immediately,

re-adjust the gas line regulator and/or install a larger gas

supply line!

If the blower inlet and/or intake hood, or flue outlet/hood is/are

blocked for any reason, the safety switches will open, which

will de-energize the flame control module.

– The spark generator is off.

– The flame module monitors pilot flame current. Should the

flame failure occur during the Heating Mode, the unit will start

again from purging cycle.

– Thermostat is satisfied, switch opens.

– Power is interrupted to the flame control module and blower

motor. Gas valves are closed.

– Heater is in Standby Mode.

– Thermostat is satisfied, switch opens.

– Power is interrupted to burner, turning off blower and ignition

control module. Solenoid and main gas valves are closed.

– Insufficient blower pressure causes safety pressure switches

to open.

wATEr TEMPErATUrE CONTrOL