3-24. External Electronic Expansion Valve Kit (ATK-SVRK56BA)

Precautions in this manual are given in the form of "Warnings" or "Cautions." Both types of precautions contain
important information related to your safety, the safety of users, and the correct operation, installation,
or maintenance of the air conditioning system. Be sure to carefully observe all relevant precautions.

This symbol refers to a hazard or unsafe practice which can result in severe personal injury
or death.

This symbol refers to a hazard or unsafe practice which can result in personal injury or product
or property damage.

• This external electronic expansion valve is compatible with the refrigerants listed below.

R410A, R407C, R22

1. Checking Parts

Please check these parts below that came in the box.

Description

Shape

Q'ty

Description

Shape

Q'ty

1

External electronic

expansion valve

(Extension cord 26.2 ft.)

1

3

Clamp
(Large: 13-25/32",
Small: 7-7/8")

Large: 2

Small: 4

4

Installation manual

1

2

Flare insulator

2

5

Insulating tape

White
(heat resisting)

2

2. Positioning for Installation

• The valve should be connected to the liquid tube. Determine the position for installation referring to the diagram of

outer dimensions. (Fig. 3-52) Refrigerant-flow noise may occur from the external electronic expansion valve. As a

guide, the distance from the indoor unit should be a minimum of 16.4 feet, but less than 26.2 feet. (Install away from

locations where strictly quiet operation is required.)

If this distance is unavailable, install inside the ceiling or in another location where noise insulation is possible.

This is a functional component, and therefore may require inspection and replacement. Consider this when deciding

the installation location. (For example, place near an inspection port, or provide one.)

• This valve is for indoor use. Do not install the valve outdoors.

Diagram of outer dimensions

CAUTION

WARNING

(8-5/64)

Type

A
B

56

12-51/64

o 1/4

160

14-11/64

o 3/8

A

(10-53/64)

Extension cord (26.2 ft.)

Connecting portion B

Connecting portion B

Outdoor

side

Indoor

side

(2-3/4)

Fig. 3-52

Unit: in.