Fig. 3-14 – Sanyo ECO R410A User Manual
Page 12
12
Fig. 3-14
Inter-unit control wiring
Power supply outlet
(4) When the check of drainage is complete, open the check pin (CHK)
and remount the insulator and drain cap onto the drain inspection port.
CAUTION
Be careful since the fan will start when you
short the pin on the indoor control board.
706
Exter
nal Static Pressure
0
353
Limit line
HT
H
L
M
1059
883
1413
Exter
nal Static Pressure
706
Limit line
L
M
H
HT
1059
Exter
nal Static Pressure
494 565
706
742
918
Limit line
HT
L
M
H
177
247 306
Air Flow (CFM)
Exter
nal Static Pressure
0
353
HT
H
M
L
530
Air Flow (CFM)
Exter
nal Static Pressure
0
353
371
318
428
Limit line
Limit line
HT
M
L
H
1059
883
1413
Exter
nal Static Pressure
706
Limit line
Limit line
L
M
H
HT
UHX0762
UHX0962
UHX1262
UHX1562
UHX1862
UHX2462
UHX3662
UHX4862
UHX5462
0.60
Limit line
Limit line
Limit line
Limit line
(in.WG)
0.40
0.20
0.60
(in.WG)
0.40
0.20
0.60
(in.WG)
0.40
0.20
Limit line
Air Flow Volume (CFM)
0
0.60
(in.WG)
0.40
0.20
0
0.60
(in.WG)
0.40
0.20
0
0.60
(in.WG)
0.40
0.20
Air Flow Volume (CFM)
Air Flow Volume (CFM)
Air Flow Volume (CFM)
(1) Remove 4 screws on the electrical component box and
remove the cover plate.
(2) Disconnect the fan motor sockets in the box.
(3) Take out the booster cable (sockets at both ends)
clamped in the box.
(4) Securely connect the booster cable sockets between the
disconnected fan motor sockets in step 2 as shown in
Fig. 3-15.
(5) Place the cable neatly in the box and reinstall the cover
plate.
Fig. 3-15
Fig. 3-16
Booster cable
Booster cable
Electrical component box
(At shipment)
(Booster cable installed)
Fan motor socket
Fan
motor
How to read the diagram
The vertical axis is the external static pres-
sure (in. WG) while the horizontal axis rep-
resents the air flow (CFM). The characteris-
tic curves for “HT,” “H,” “M” and “L” fan speed
control are shown.
The nameplate values are shown based on
the “H” air flow. For the 18 and 24 types, the
air flow is 635 CFM, while the external static
pressure is 0.20 in. WG at “H” position. If
external static pressure is too great (due
to long extension of ducts, for example),
the air flow volume may drop too low at
each air outlet. This problem may be solved
by increasing the fan speed as explained
above.
3-5. Increasing the Fan Speed
If external static pressure is too great (due to long extension of ducts, for
example), the air flow volume may drop too low at each air outlet. This problem
may be solved by increasing the fan speed using the following procedure:
HT : Using the booster cable
T : At shipment
NOTE