3-13. Installing the Drain Piping

(1) Prepare standard hard PVC pipe (O.D. 1-1/32") for

the drain and use the supplied hose band to prevent
water leaks.
The PVC pipe must be purchased separately. The
transparent drain part on the unit allows you to check
drainage.

CAUTION

Do not use adhesive at the drain connection port on

the indoor unit.

Insert the drain pipe until it contacts the socket, as

shown in the figure at right, then secure it tightly with
the hose band.

Do not use the supplied drain hose bent at a 90°

angle. (The maximum permissible bend is 45°.)

Tighten the hose clamps so their locking nuts face in

the horizontal direction.

Make sure that the drain port is not a downward gra-

dient from the joint section (may lead to abnormal
noise).

NOTE

Make sure the drain pipe has a downward gradient
(1/100 or more) and that there are no water traps.

If it is necessary to increase the height of the drain

pipe, the section directly after the connection port can
be raised a maximum of 19-11/16". Do not raise it any
higher than 19-11/16", as this could result in water
leaks.

Do not install the pipe with an upward gradient from the

connection port. This will cause the drain water to flow
backward and leak when the unit is not operating.

Do not apply force to the piping on the unit side when con-

necting the drain pipe. The pipe should not be allowed to
hang unsupported from its connection to the unit.
Fasten the pipe to a wall, frame, or other support as close
to the unit as possible.

3-14. Checking the Drainage

After wiring and drain piping are completed, use the follow-
ing procedure to check that the water will drain smoothly. For
this, prepare a bucket and wiping cloth to catch and wipe up
spilled water.

(1) Connect power to the power terminal board (R, S termi-

nals) inside the electrical component box.

(2) Remove the eyelet cap and through the opening, slowly

pour about 0.13gal of water into the drain pan to check
drainage.

(3) Short the check pin (CHK) on the indoor control board and

operate the drain pump. Check the water flow through the
transparent drain port and see if there is any leakage.

CAUTION

Do not install an air bleeder as

this may cause water to spray
from the drain pipe outlet.

CAUTION

Attach so that the hose

band fastener is on the side
of the drain port.

Attach the hose bands so

that each is approximately
1/4" to 1" from the end of
the supplied drain hose.

5-33/64

1

1

13/64

13/64

Twist tie
(4 ties, supplied)

Drain port

Drain hose
insulation
(supplied)

Hard PVC pipe
(equivalent to
O.D. 1-1/32")
(Field supply)

Position to
fasten hose
bands

Hose band
(2 bands, supplied)

Drain hose
(supplied)

Unit

Unit: in.

Prohibited

Air bleeder

11-13/16" or less
(not a downward gradient)

19-11/16" or less

at least 1/100

Good

Prohibited

Upward gradient

Support pieces

Fig. 3-29

Fig. 3-30

Fig. 3-31

Fig. 3-32

Fig. 3-33