7. SPECIFICATIONS

English

© Siemens plc 1997

G85139-H1750-U049-B

35

26/09/97

7. SPECIFICATIONS

230 V Single Phase MICROMASTER Inverters

Order No. (6SE92 ..)

10-7BA40

11-5BA40

12-1BA40

12-8BA40

13-6BA40

15-2BB40

16-8BB40

21-0BC40

21-3BC40

Inverter model

MM12

MM25

MM37

MM55

MM75

MM110

MM150

MM220

MM300

c

Input voltage range

1 AC 230 V +/-15% 2 AC 208 V +/-10%

Motor output rating

a

(kW / hp)

0.12 /

1

/

6

0.25 /

1

/

3

0.37 /

1

/

2

0.55 /

3

/

4

0.75 / 1

1.1 / 1

1

/

2

1.5 / 2

2.2 / 3

3.0 / 4

Continuous output

350 VA

660 VA

920 VA

1.14 kVA

1.5 kVA

2.1 kVA

2.8 kVA

4.0 kVA

5.2 kVA

Output current (nom.)

a

0.75 A

1.5 A

2.1 A

2.6 A

3.5 A

4.8 A

6.6 A

9.0 A

11.8 A

Output current (max. continuous)

0.8 A

1.7 A

2.3 A

3.0 A

3.9 A

5.5 A

7.4 A

10.4 A

13.6 A

Input current (I rms)

1.8 A

3.2 A

4.6 A

6.2 A

8.2 A

11.0 A

14.4 A

20.2 A

28.3 A

Recommended mains fuse

10 A

16 A

20 A

25 A

32 A

Recommended lead

Input

1.0 mm

2

1.5 mm

2

2.5 mm

2

4.0 mm

2

cross-section (min.)

Output

1.0 mm

2

1.5 mm

2

2.5 mm

2

Dimensions (mm) (w x h x d)

73 x 175 x 141

149 x 184 x 172

185 x 215 x 195

Weight (kg / lb)

0.85 / 1.9

2.6 / 5.7

5.0 / 11.0

All 1 AC 230 V MICROMASTERS include integrated Class A filters. Optional external Class B filters are available (see section 8.3).

230 V 3 Phase MICROMASTER Inverters

Order No. (6SE92 ..)

10-7CA40 11-5CA40 12-1CA40 12-8CA40 13-6CA40 15-2CB40 16-8CB40 21-0CC40

21-3CC40

21-8CC13

Inverter model

MM12/2

MM25/2

MM37/2

MM55/2

MM75/2

MM110/2

MM150/2

MM220/2 MM300/2

c

MM400/2

Input voltage range

1 - 3 AC 230 V +/-15%

3 AC

Motor output rating

a

(kW / hp)

0.12 /

1

/

6

0.25 /

1

/

3

0.37 /

1

/

2

0.55 /

3

/

4

0.75 / 1

1.1 / 1

1

/

2

1.5 / 2

2.2 / 3

3.0 / 4

4.0 / 5

Continuous output

350 VA

660 VA

920 VA

1.14 kVA

1.5 kVA

2.1 kVA

2.8 kVA

4.0 kVA

5.2 kVA

7.0 kVA

Output current (nom.)

a

0.75 A

1.5 A

2.1 A

2.6 A

3.5 A

4.8 A

6.4A

9.0 A

11.8 A

15.9 A

Output current (max. continuous)

0.8 A

1.7 A

2.3 A

3.0 A

3.9 A

5.5 A

7.0 A

10.4 A

13.6 A

17.5 A

Input current (I rms) (1 AC / 3 AC)

1.8 / 1.1 A

3.2 / 1.9 A

4.6 / 2.7 A

6.2 / 3.6 A

8.2 / 4.7 A

11.0 / 6.4 A

14.4 / 8.3 A

20.2 / 11.7 A

28.3 / 16.3 A

- / 21.1 A

Recommended mains fuse

b

10 A

16 A

20 A

25 A

Recommended lead

Input

1.0 mm

2

1.5 mm

2

2.5 mm

2

4.0 mm

2

cross-section (min.)

Output

1.0 mm

2

1.5 mm

2

2.5 mm

2

Dimensions (mm) (w x h x d)

73 x 175 x 141

149 x 184 x 172

185 x 215 x 195

Weight (kg / lb)

0.75 / 1.7

2.4 / 5.3

4.8 / 10.5

All 1 AC and 3 AC 230 V MICROMASTERS (excluding MM400/2) are suitable for 208 V operation.
All 3 AC 230 V MICROMASTERS can operate on 1 AC 230 V (MM300/2 requires an external line choke, e.g. 4EM6100-3CB).

380 V - 500 V Three Phase MICROMASTER Inverters

Order No. (6SE92 ..)

11-1DA40

11-4DA40 12-0DA40 12-7DA40 14-0DA40 15-8DB40 17-3DB40 21-0DC40 21-3DC40 21-5DC40

Inverter model

MM37/3

MM55/3

MM75/3

MM110/3

MM150/3

MM220/3

MM300/3

MM400/3

MM550/3

MM750/3

Input voltage range

3 AC 380 V - 500 V +/-10%

Motor output rating

a

(kW / hp)

0.37 /

1

/

2

0.55 /

3

/

4

0.75 / 1

1.1 / 1

1

/

2

1.5 / 2

2.2 / 3

3.0 / 4

4.0 / 5

5.5 / 7

1

/

2

7.5 / 10

Continuous output

930 VA

1.15 kVA

1.5 kVA

2.1 kVA

2.8 kVA

4.0 kVA

5.2 kVA

7.0 kVA

9.0 kVA

12.0 kVA

Output current (nom.) (400 V / 500 V)

a

1.05/0.95A

1.5 / 1.3 A

2.0 / 1.8 A

2.8 / 2.5 A

3.7 / 3.3 A

5.2 / 4.6 A

6.8 / 6.0 A

9.2 / 8.1 A

11.8 / 10.4 A

15.8 / 13.9 A

Output current (max. continuous)

1.2/ 1.06 A 1.6 /1.45 A 2.1 / 1.9 A

3.0 / 2.7 A

4.0 / 3.6 A

5.9 / 5.3 A

7.7 / 6.9 A

10.2 / 9.1A

13.2/ 11.8 A

17.0 / 15.2 A

Input current (I rms)

2.2 A

2.8 A

3.7 A

4.9 A

5.9 A

8.8 A

11.1 A

13.6 A

17.1 A

22.1 A

Recommended mains fuse

10 A

16 A

20 A

25 A

Recommended lead

Input

1.0 mm

2

1.5 mm

2

2.5 mm

2

4.0 mm

2

cross-section (min.)

Output

1.0 mm

2

1.5 mm

2

2.5 mm

2

Dimensions (mm) (w x h x d)

73 x 175 x 141

149 x 184 x 172

185 x 215 x 195

Weight (kg / lb)

0.75 / 1.7

2.4 / 5.3

4.8 / 10.5

Optional external Class A and Class B filters are available (see section 8.3).

Notes

a

Siemens 4 pole-motor, 1LA5 series or equivalent.

b

Assumes 3-phase supply. If a single phase supply is used, the input current ratings, wire sizes and fuses for single phase

MICROMASTERS will apply.

c

MM300 and MM300/2 require an external choke (e.g. 4EM6100-3CB) and a 30 A mains fuse to operate on a single phase supply.