6. FAULT CODES

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

34

6. FAULT CODES

In the event of a failure, the inverter switches off and a fault code appears on the display. The last fault that
occurred is stored in parameter P930. e.g. ‘0003’ indicates that the last error was F003.

Fault Code

Cause

Corrective Action

F001

Overvoltage

Check whether supply voltage is within the limits indicated on the rating plate.
Increase the ramp down time (P003).
Check whether the required braking power is within the specified limits.

F002

Overcurrent

Check whether the motor power corresponds to the inverter power.
Check that the cable length limits have not been exceeded.
Check motor lead and motor for short-circuits and earth faults.
Check whether the motor parameters (P081 - P086) correspond with the
motor being used.
Check the stator resistance (P089).
Increase the ramp-up time (P002).
Reduce the boost set in P078 and P079.
Check whether the motor is obstructed or overloaded.

F003

Overload

Check whether the motor is overloaded.
Increase the maximum motor frequency if a motor with high slip is used.

F005

Inverter overtemperature
(internal PTC)

Check that the ambient temperature is not too high.
Check that the air inlet and outlet are not obstructed.
Check that the integral fan is working.

F008

USS protocol timeout

Check the serial interface.
Check the settings of the bus master and P091 - P093.
Check whether the timeout interval is too short (P093).

F010

Initialisation fault / Parameter loss *

Check the entire parameter set. Set P009 to ‘ 0000’ before power down.

F011

Internal interface fault *

Switch off power and switch on again.

F012

External trip (PTC)

Check if motor is overloaded.

F013

Programme fault *

Switch off power and switch on again.

F018

Auto-restart after fault.

Automatic re-start after fault (P018) is pending.
WARNING:

The inverter may start at any time.

F030

PROFIBUS link failure

Check the integrity of the link.

F031

Option module to link failure

Check the integrity of the link.

F033

PROFIBUS configuration error

Check the PROFIBUS configuration.

F036

PROFIBUS module watchdog trip

Replace PROFIBUS module

F074

Motor overtemperature by I

2

t

calculation

Check that the motor current does not exceed the value set in P083.

F106

Parameter fault P006

Parameterise fixed frequency(ies) and/or motor potentiometer on the digital
inputs.

F112

Parameter fault P012/P013

Set parameter P012 < P013.

F151 - F153

Digital input parameter fault

Check the settings of digital inputs P051 to P053.

F188

Automatic calibration failure

Motor not connected to inverter - connect motor.

If the fault persists, set P088 = 0 and then enter the stator resistance of the
motor into P089 manually.

F201

P006 = 1 while P201 = 2

Change parameter P006 and/or P201.

F212

Parameter fault P211/P212

Set parameter P211 < P212.

*

Ensure that the wiring guidelines described in section 2.1 have been complied with.

When the fault has been corrected the inverter can be reset. To do this press button P twice (once to display P000 and the second
time to reset the fault), or erase the fault via a binary input (see parameters P051 - P053 in section 5) or via the serial interface.