beautypg.com

English 2. installation, 4 control connections – Siemens G85139 User Manual

Page 12

background image

English

2. INSTALLATION

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

12

2.3.4 Control Connections

1

2

3

4

8

5

6

7

9

10

11

Power Supply

(+10 V, max. 10 mA)

Analogue Input

(0/2 - 10 V)

(input impedance = 70 k

)

Output Relay

(normally open)

max. 0.4 A / 110 V AC

1 A / 30 V DC

(resistive rating)

Digital Inputs

(7.5 - 33 V, max. 5 mA)

Power Supply

for

PI Feedback

Transducer or other

load

(+15 V, max. 50 mA)

P10+

0V

AIN+

AIN-

P15+

DIN1

DIN2

DIN3

RL1B

(NO)

RL1C

(COM)

0V

Control Terminal Block

Insert small blade screwdriver
(max. 3.5 mm) as shown while
inserting control wire from below.

Front Panel

RS485 D-type

N-

0V

5V

(max.250 mA)

P+

6

1

5

9

Figure 6: Control Connections