5. SYSTEM PARAMETERS

Parameter

Function

Range

[Default]

Description / Notes

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

26

P051

Selection control function, DIN1

0 - 19

(terminal 5), fixed frequency 3

[1]

or binary fixed frequency bit 0.

P052

Selection control function, DIN2

0 - 19

(terminal 6), fixed frequency 2.

[2]

or binary fixed frequency bit 1.

P053

Selection control function, DIN3

0 - 19

(terminal 7), fixed frequency 1
or binary fixed frequency bit 2.

[6]

Value

0
1
2
3
4
5
6
7
8
9

10

11
12
13

14

15
16
17

18

19

Function of P051 to P053

Input disabled
ON right
ON left
Reverse
OFF2 **
OFF3 **
Fixed frequencies 1 - 3
Jog right
Jog left
Remote operation
Fault code reset

Increase frequency *
Decrease frequency *
Disable analogue input
(setpoint is 0.0 Hz)
Disable the ability to change
parameters
Enable dc brake
Do not use
Binary fixed frequency control
(fixed frequencies 1 - 7)
As 6, but input high will also
request RUN *
External trip/PTC

Function,

low state

-

Off
Off
Normal
OFF2
OFF3
Off
Off
Off
Local
Off

Off
Off
Analogue on

enabled

Off
-
Off

Off

Yes (F012)

Function,

high state

-

On right
On left
Reverse
On
On
On
Jog right
Jog left
Remote
Reset on
rising edge
Increase
Decrease
Analogue
disabled
disabled

Brake on
-
On

On

No

*

Only effective when P007 = 0.

** See section 4.3.

Binary Coded Fixed Frequency Mapping

(P051, P052, P053 = 17)

DIN3

(P053)

DIN2

(P052)

DIN1

(P051)

STOP

0

0

0

RUN to FF1 (P041)

0

0

1

RUN to FF2 (P042)

0

1

0

RUN to FF3 (P043)

0

1

1

RUN to FF4 (P044)

1

0

0

RUN to FF5 (P046)

1

0

1

RUN to FF6 (P047)

1

1

0

RUN to FF7 (P048)

1

1

1

P056

Digital input debounce time

0 - 2

[0]

0 = 12.5 ms
1 = 7.5 ms
2 = 2.5 ms