English

5. SYSTEM PARAMETERS

Parameter

Function

Range

[Default]

Description / Notes

G85139-H1750-U049-B

© Siemens plc 1997

26/09/97

32

P210

Transducer reading (%)

0.0 - 100.0

[-]

Read only. Value is a percentage of full scale of the selected input.

P211

0% setpoint

0.00-100.00

[0.00]

Value of P210 to be maintained for 0% setpoint.

P212

100% setpoint

0.00-100.00

[100.00]

Value of P210 to be maintained for 100% setpoint.

P220

PI frequency cut-off

0 - 1

[0]

0 = Normal operation
1 = Switch off inverter output at or below minimum frequency.

P700

P701

P702

P880

P910

Local/Remote mode

0 - 4

[0]

Sets the inverter for local control or remote control over the serial link:

0 = Local control
1 = Remote control (and setting of parameter values)
2 = Local control (but remote control of frequency)
3 = Remote control (but local control of frequency)
4 = Local control (but remote read and write access to

parameters and facility to reset trips)

Note:

When operating the inverter via remote control (P910 = 1
or 3), the analogue input remains active when P006 = 1
and is added to the setpoint.

P918

Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details

.

Access only possible with P099 = 1

P922

Software version

0.00 - 99.99

[-]

Contains the software version number and cannot be changed.

P923

Equipment system number

0 - 255

[0]

You can use this parameter to allocate a unique reference number to
the inverter. It has no operational effect.

P927

Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details

.

P928

Access only possible with P099 = 1

P930

Most recent fault code

0 - 9999

[-]

The last recorded fault code (see section 6) is stored in this parameter.
This parameter can be cleared using the

and

buttons.

P931

Most recent warning type

0 - 9999

[-]

The last recorded warning is stored in this parameter until power is
removed from the inverter:

002 = Current limit active
003 = Voltage limit active
005 = Inverter over-temperature (Internal PTC)

P944

Reset to factory default settings

0 - 1

[0]

Set to ‘1’ and then press P to reset all parameters except P101 to the
factory default settings.

Specific to PROFIBUS-DP. See PROFIBUS Handbook for further
details.
Access only possible with P099 = 1