5. SYSTEM PARAMETERS

English

Parameter

Function

Range

[Default]

Description / Notes

© Siemens plc 1997

G85139-H1750-U049-B

33

26/09/97

P947

P958

P963

Specific to PROFIBUS-DP. See PROFIBUS Handbook for further

P967

details.

P968

Access only possible with P099 = 1

P970

P971

EEPROM storage control

0 - 1

[1]

0 = Changes to parameter settings (including P971) are lost when

power is removed.

1 = Changes to parameter settings are retained during periods

when power is removed.

WARNING:

When using the serial link to update the parameter
set held in EEPROM, care must be taken not to
exceed the maximum number of write cycles to this
EEPROM - this is approximately 50,000 write cycles.
Exceeding this number of write cycles would result
in corruption of the stored data and subsequent
data loss. The number of read cycles are unlimited.