P061, P062, P063 – Siemens G85139 User Manual

Page 27: P064, P065, System parameters english

background image

5. SYSTEM PARAMETERS

English

Parameter

Function

Range

[Default]

Description / Notes

© Siemens plc 1997

G85139-H1750-U049-B

27

26/09/97

P061

Selection relay output RL1

0 - 13

[6]

Value Relay function

Active

3

0

No function assigned (relay not active)

Low

1

Inverter is running

High

2

Inverter frequency 0.0 Hz

Low

3

Motor run right has been selected

High

4

External brake on (see parameters P063/P064)

Low

5

Inverter frequency less than or equal to minimum
frequency

Low

6

Fault indication

1

Low

7

Inverter frequency greater than or equal to setpoint

High

8

Warning active

2

Low

9

Output current greater than or equal to P065

High

10

Motor current limit (warning)

2

Low

11

Motor over temperature (warning)

2

Low

12

Closed loop motor LOW speed limit

High

13

Closed loop motor HIGH speed limit

High

1

Inverter switches off (see parameter P930 and section 6).

2

Inverter does not switch off (see parameter P931).

3

‘Active low’ = relay OPEN. ‘Active high’ = relay CLOSED.

P062

Electro-mechanical brake option
control

0 - 4

[0]

This operates in the same manner as the external brake control
(described in P063/P064), except that the relay is not activated.

0 =

Normal stop mode

1 - 3 = Do not use
4 =

Combination stop mode

P063

External brake release delay
(seconds)

0 - 20.0

[1.0]

Only effective if the relay output is set to control an external brake (P061 =
4). In this case when the inverter is switched on, it will run at the minimum
frequency for the time set by this parameter before releasing the brake
control relay and ramping up (see illustration in P064).

P064

External brake stopping time
(seconds)

0 - 20.0

[1.0]

As P063, only effective if the relay output is set to control an external
brake. This defines the period for which the inverter continues to run at
the minimum frequency after ramping down and while the external
brake is applied.

Notes:

(1)

Settings for P063 and P064 should be slightly longer
than the actual time taken for the external brake to
apply and release respectively.

(2)

Setting P063 or P064 to too high a value, especially
with P012 set to a high value, can cause an
overcurrent warning or trip as the inverter attempts to
move a locked motor shaft.

P065

Current threshold for relay (A)

0 - 99.9

[1.0]

This parameter is used when P061 = 9. The relay switches on when
the motor current is greater than the value of P065 and switches off
when the current falls to 90% of the value of P065 (hysteresis).

ON

OFF

t

P063

A

t

P064

A

f

f

min

B

t

A = Brake applied
B = Brake removed