SMC Networks EX500 User Manual
Page 8
EX500 Serial System
EX## - OME0008
- 7 -
3. Specification and Product numbers
3 -1. General specification of EX500 series
Item
Specification
Enclosure
IP65
Standard
UL,CSA,CE
Withstand voltage
1500V AC 1min. ( between PE - external terminal package )
Insulation resistance
2MΩor more
( 500VDC meg. between PE - external terminal package )
Momentary power failure
1m sec. or less
Ambient temperature
+5℃ to +45℃
Ambient humidity
35% to 85%RH ( without condensation )
Preservation temperature
- 25℃ to 70℃
Vibration proof
10Hz to 57Hz 0.35mm ( constant amplitude )
57Hz to 150Hz 5G ( constant speed )
2 hours per each direction of ±X,Y and Z
Shock resistance
Peak value : 15G
3 times per each direction of ±X,Y and Z
Applicable altitude
Less than 1000m above sea
・
・・
・
EMC Directive ( 89 / 336 / EEC )
EN50081-2 / 1993, EN55011 / 1998 +A1 : 1999, EN50082-2 / 1995, EN61000-6-2 / 1999
Electromagnetic Emission
Item
Test Procedure
Specification
Criterion
Radiated Electric Field
Strength
EN55011 : 1998 +A1
: 1999
30MHz to 230MHz, 230MHz to 1GHz
( Distance : 10m )
Group 1
Class A
Electromagnetic Susceptibility ( Immunity )
Item
Test Procedure
Specification
Criterion
ESD
EN61000-4-2 : 1995 /
A1 : 1998
±
4kV contact
±
8kV air discharge
B
RS :
Radiated Susceptibility
( amplitude modulated)
EN61000-4-3 : 1996 /
A1 : 1998
80MHz to 1000MHz
10V / m ( 1kHz AM 80% )
A
RS :
Radiated Susceptibility
( pulse modulated )
ENV50204 : 1995
900±5MHz
10V / m
( 200Hz Pulse Mod. Duty 50% )
A
CS :
Conductive
Susceptibility
( amplitude modulated)
EN61000-4-6 : 1996
0.15MHz to 80 MHz
10V ( 1kHz AM 80% )
A
EFT / Burst,
DC power lines
EN61000-4-4 : 1995
±
2kV
( 5 / 50ns, 5kHz )
B
EFT / Burst,
control lines
EN61000-4-4 : 1995
±
2kV
( 5 / 50ns, 5kHz )
B
Surge,
interface lines
EN61000-4-5 : 1995
±
1kV ( Common )
B