beautypg.com

SMC Networks EX500 User Manual

Page 11

background image

EX500 Serial System

EX## - OME0008

- 10 -

PROFIBUS-DP communication specification ( EX500 - GPR1 )

Item

Specification

Protocol

PROFIBUS-DP ( EN50170 )

Bus interface

EIA RS - 485

Communication speed

9.6 / 19.2 / 93.75 / 187.5 / 500 k bit / sec.
1.5 / 3 / 6 / 12 M bit / sec.

Cable distance

Refer to section 6 -1

Freeze function

Available

Synchronous function

Available

ID number

1405 hex
M12 connector ( 5 pin, plug )

Communication connector

IN
Pin NO.
1. VP
2. RxD / TxD ( N )
3. DGND
4. RxD / TxD ( P )
5. Shield

OUT
Pin NO.
1. N.C.
2. RxD / TxD ( N )
3. N.C.
4. RxD / TxD ( P )
5. Shield

2

3

5

1

4

For GW Unit