beautypg.com

SMC Networks EX500 User Manual

Page 22

background image

EX500 Serial System

EX## - OME0008

- 21 -

5. How to operate EX500 - GDN1 ( DeviceNet )

5 -1. Connection style

DeviceNet unit can be connected by T branch, Multi branch and Branch line branch.
Total extension length of trunk and stay is different depending on communication speed and thickness of

communication cable.

EX500 series can be connected only by T branch.


・・

Wiring length

Communication speed ( k bit / sec. )

125

250

500

Thick cable

500m or less

250m or less

100m or less

Max. length

of

Network

Thin cable

100m or less

156m or less

78m or less

39m or less

Total length of branch line

Note : Max. length of a branch line is up to 6m.

Terminating resistance

121 ohms, 1/2W ( TURCK p / n = RSM57TR2 )

・・

Cable specification

Thick cable

Thin cable

Item

Signal

Power

Signal

Power

Conductor

section area

0.82mm

2

1.65mm

2

0.20mm

2

0.33mm

2

Color

Blue ( CAN-L )

White ( CAN-H )

Red ( 24VDC ),

Black ( 0VDC )

Blue, White

Red, Black

Impedance

120 ohms±10%

-

120 ohms±10%

-

Propagation

delay

( Maximum )

1.36ns / ft

-

1.36ns / ft

-

500kHz : 0.25dB / ft

500kHz : 0.50dB / ft

125kHz : 0.13dB / ft

125kHz : 0.29dB / ft

Attenuation

rate

( Maximum )

1.00MHz : 0.40dB / ft

-

1.00MHz : 0.70dB / ft

-

Conductor
resistance

( Maximum )

6.9 ohms / 1000ft

3.6 ohms / 1000ft

28 ohms / 1000ft

17.5 ohms / 1000ft

1ft ≒ 0.3048m

Terminating resistance

Multi branch

Branch line

T branch

Main

Branch line branch

Max. 6m

Node

Node

Node

Branch line

Branch line

Node

Node

Node

Node

Node

Node

Terminating resistance

Multi

branch

Multi branch