Remedies
1
The status of MS LED
Operating in a normal condition
: Green lights
Recoverable fault
( Memory is abnormal ) : Red lights
・
Check the signal line from PLC is properly connected.
( Refer to section 5 -2 )
・
Check Wiring and pin out.
( Refer to section 3 -2, 3 -6 -1 )
・
Check communication speed and Address setting switch
are correctly set.
( Refer to section 5 -4 )
2
The status of NS LED
Not online : Lights off
Online , Not Allocated
: Green flashing
Online , Allocated : Green lights
Connection Time - Out
: Red flashing
Critical Link Failure : Red lights
・
Check the signal line from PLC is properly connected.
( Refer to section 5 -2 )
・
Check wiring and pin out.
( Refer to section 3 -2, 3 -6 -1 )
・
Check communication speed and Address setting switch
are correctly. ( Refer to section 5 -4 )
3
SOL LED lights off.
・
Check power supply to make sure that 24VDC is supplied
to solenoid valve. ( Refer to section 9 -1 )
・
Check power supply to solenoid valves is not less
than 20VDC.
・
・・
・
PROFIBUS-DP communication
NO.
Item
Remedies
1
RUN LED lights off.
・
Check the power supply is supplying 24V DC.
( Refer to section 9 -1 )
2
BF LED lights.
・
Check the signal line from PLC is properly connected.
( Refer to section 6 -2 )
・
Check wiring and pin out.
( Refer to section 3 -2 )
・
Check Address setting switch is correctly set.
( Refer to section 6 -4 -1 )
・
Check the terminating resistance is correctly set.
( Refer to section 6 -4 -2 )
3
DIA LED lights.
・
Check the power supply for the solenoid valve is supplying.
( Refer to section 9 -1 )
・
Check the power supply for the solenoid valve is not less
than 20VDC.
4
SOL LED lights off.
・
Check the power supply for the solenoid valve is supplying.
( Refer to section 9 -1 )
・
Check the power supply for the solenoid valve is not less
than 20VDC.