5 -3. led display, 5 -4. operation setting – SMC Networks EX500 User Manual

Page 24

background image

EX500 Serial System

EX## - OME0008

- 23 -

5 -3. LED display

When the Input Unit Manifold is not connected, the respective COM LED of the GW Unit will not light up.
To monitor the status of COM port, it is necessary to use a Terminal Plug.
The COM LED will light up when a Terminal Plug is used. ( Refer to section 3 -6 -4 )

5 -4. Operation setting

Turn the power supply OFF when setting switches.

Open the station switch protection cover and set the rotary switch with a flat blade screw driver.

COM A COM B COM C COM D

SOL

NS

MS

BUS

GATEWAY UNIT
EX500 SERIES

Display

Content

MS

Operating in a normal condition : Green lights
Recoverable fault ( Memory is abnormal ) : Red lights

NS

Not online : Lights off
Online , Not Allocated : Green flashing
Online , Allocated : Green lights
Connection Time - Out : Red flashing
Critical Link Failure : Red lights

SOL

Solenoid valve source voltage is normal : Lights
Voltage lowered to 20V or less : Lights off

COM A

Communication port A is receiving data : Lights
Communication port A has no data : Lights off

COM B

Communication port B is receiving data : Lights
Communication port B has no data : Lights off

COM C

Communication port C is receiving data : Lights
Communication port C has no data : Lights off

COM D

Communication port D is receiving data : Lights
Communication port D has no data : Lights off

0

1

2

3

4

5

9

8

7

6

Figure of setting switch

SW1

SW3

SW2

CAUTION