beautypg.com

6 -2. parts description, Terminating resistance, Cable specification – SMC Networks EX500 User Manual

Page 26: Communication speed and longest wiring length, Ex500 serial system, Or more, Caution

background image

EX500 Serial System

EX## - OME0008

- 25 -

6. How to operate EX500 - GPR1 ( PROFIBUS-DP )

6 -1. Communication wiring

A twisted pair cable with shield is used in the
communication wiring of PROFIBUS- DP.
A maximum length of cable depend on
communication speed.
The specification of cable length is based on
TYPE A cable which has parameters shown below.

・・

Terminating resistance

It is necessary to attach terminating
resistance to the units located at the
ends of transmission line.
Refer to section 6 -4 -2, for setting
the terminating resistance.

6 -2. Parts description

a. Fieldbus connector

: Port for PLC connection.

b. Power supply connector

: The power source for Input Unit, SI Unit, and control and

for the solenoid valve is connected through this port.

c. Communication port

: Input Unit Manifold or the Manifold Valve with

the SI Unit is connected through this port.

d. LED display window

: The state of the power source supply and the PLC

communication is displayed. ( Refer to section 6 -3 )

e. Station switch protection cover

: Switches for the operation setting are inside.

( Refer to section 6 -4 )

The station switch protection cover should be tightened with specified tightening torque
after it is opened. ( Tightening torque : 0.6 N・m )

R

C

US

TYP

E1

EX5

00-

GPR

1

VOL

TAG

E 2

4VD

C/2

00m

A

INP

UT/

OUT

PUT

6

4/6

4

IP

COD

E

IP

65

SER

IAL

NO

.

MAD

E IN

JA

PAN

COM

D

24V

DC

DIA

BF

SOL

RUN

PE

EX5

00 S

ERIE

S

GAT

EW

AY U

NIT

IN

OUT

BUS

P

R

F

PR

OC

ESS

FIE

LD B

US

S

U

B

I

O

R

SMC

SMC

SMC

SMC

LED display window

Station switch protection cover

Communication port A
Communication port B

Communication port C
Communication port D

Power supply connector

Fieldbus connector

(PROFIBUS-DP)

Data Line

Data Line

390 ohms

220 ohms

390 ohms

VP

RxD/TxD-P

DGND

RxD/TxD-N

・・

Cable specification

Impedance

135 ohms to 165 ohms

Capacitance between

conductors

30 pF / m or less

Conductor resistance

110 ohms / km

Cable diameter

0.64 mm

Conductor area

0.34 mm

2

or more

・・

Communication speed and Longest wiring length

Communication

speed

9.6

[k bit/sec]

19.2

[k bit/sec]

93.75

[k bit/sec]

187.5

[k bit/sec]

500

[k bit/sec]

1.5

[M bit/sec]

12

[M bit/sec]

Wiring

length

1200

[m]

1000

[m]

400

[m]

200

[m]

100

[m]

CAUTION