6 -2. parts description, Terminating resistance, Cable specification – SMC Networks EX500 User Manual
Page 26: Communication speed and longest wiring length, Ex500 serial system, Or more, Caution
EX500 Serial System
EX## - OME0008
- 25 -
6. How to operate EX500 - GPR1 ( PROFIBUS-DP )
6 -1. Communication wiring
A twisted pair cable with shield is used in the
communication wiring of PROFIBUS- DP.
A maximum length of cable depend on
communication speed.
The specification of cable length is based on
TYPE A cable which has parameters shown below.
・
・・
・
Terminating resistance
It is necessary to attach terminating
resistance to the units located at the
ends of transmission line.
Refer to section 6 -4 -2, for setting
the terminating resistance.
6 -2. Parts description
a. Fieldbus connector
: Port for PLC connection.
b. Power supply connector
: The power source for Input Unit, SI Unit, and control and
for the solenoid valve is connected through this port.
c. Communication port
: Input Unit Manifold or the Manifold Valve with
the SI Unit is connected through this port.
d. LED display window
: The state of the power source supply and the PLC
communication is displayed. ( Refer to section 6 -3 )
e. Station switch protection cover
: Switches for the operation setting are inside.
( Refer to section 6 -4 )
The station switch protection cover should be tightened with specified tightening torque
after it is opened. ( Tightening torque : 0.6 N・m )
R
C
US
TYP
E1
EX5
00-
GPR
1
VOL
TAG
E 2
4VD
C/2
00m
A
INP
UT/
OUT
PUT
6
4/6
4
IP
COD
E
IP
65
SER
IAL
NO
.
MAD
E IN
JA
PAN
COM
D
24V
DC
DIA
BF
SOL
RUN
PE
EX5
00 S
ERIE
S
GAT
EW
AY U
NIT
IN
OUT
BUS
P
R
F
PR
OC
ESS
FIE
LD B
US
S
U
B
I
O
R
SMC
SMC
SMC
SMC
LED display window
Station switch protection cover
Communication port A
Communication port B
Communication port C
Communication port D
Power supply connector
Fieldbus connector
(PROFIBUS-DP)
Data Line
Data Line
390 ohms
220 ohms
390 ohms
VP
RxD/TxD-P
DGND
RxD/TxD-N
・
・・
・
Cable specification
Impedance
135 ohms to 165 ohms
Capacitance between
conductors
30 pF / m or less
Conductor resistance
110 ohms / km
Cable diameter
0.64 mm
Conductor area
0.34 mm
2
or more
・
・・
・
Communication speed and Longest wiring length
Communication
speed
9.6
[k bit/sec]
19.2
[k bit/sec]
93.75
[k bit/sec]
187.5
[k bit/sec]
500
[k bit/sec]
1.5
[M bit/sec]
12
[M bit/sec]
Wiring
length
1200
[m]
1000
[m]
400
[m]
200
[m]
100
[m]
!
!
!
!
CAUTION