beautypg.com

Trouble shooting – SMC Networks EX500 User Manual

Page 39

background image

EX500 Serial System

EX## - OME0008

- 38 -

11. Trouble shooting

・・

Whole system

NO.

Item

Remedies

1

The solenoid valve does not work.

Check the power supply for the solenoid valve is supplying

24VDC. ( Refer to section 9 -1 )

Check the Branch Cable with M12 Connector is properly

connected with the SI Unit. ( Refer to section 8 -1 )

Check the Power LED and the Communication LED of

the SI Unit light up. ( Refer to section 8 -1 )

2

The solenoid valve does not work
as in the program.

Check the wiring specification of Manifold Block Ass'y.

( Refer to section 8 -2 )

3

The Power LED of the Input Unit
is flashing.

There is possibility that the input sensor has a short-circuit .

Check that the sensor is not bad.

Check the power supply for a possibility that the current in

power supply line is above the specification.

4

Connecting sensor does not start
signal.

Check the power supply to make sure that 24VDC is

supplied. ( Refer to section 9 -1 )

Check whether or not the Indicator LED of each block

lights up. ( Refer to section 7 -1 )

5

COM A - D does not light.

Check whether or not the Input Unit is connected with the

branch of the COM port which does not light up.
Check the Branch Cable with M12 Connector is properly
connected with the Input Unit. ( Refer to section 7 -1 )

Check that a Terminal Plug is connected with port C1 or C0

if Input Unit Manifold, is not connected.
( Refer to section 9 -2 -2 )

・・

Remote I/O communication

NO.

Item

Remedies

1

RUN LED lights off.

Check the power supply is supplying 24VDC.

( Refer to section 9 -1 )

2

COM LED lights off.
ERR LED lights.

Check the signal line from PLC is properly connected.

( Refer to section 4 -2 )

Check wiring and pin out. ( Refer to section 3 -2 )

Check the RACK Address is correctly set.

( Refer to section 4 -4 -1 )

Check Starting Quarter is correctly set.

( Refer to section 4 -4 -1 )

Check Data Rate is correctly set.

( Refer to section 4 -4 -2 )

Check Last RACK is correctly set.

( Refer to section 4 -4 -2 )

Check the terminating resistance is correctly set.

( Refer to section 4 -4 -3 )

3

SOL LED lights off.

Check the power supply for 24VDC ( Refer to section 9 -1 )

Check the power supply for the solenoid valve is not less

than 20V.