Battery module power module, Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual
Page 58
4.5
Hot Swapping the Battery Module
Figure 4-3: Rear view of the battery module.
EX 5/7/11 RT System
Maintenance
4 — 6
86-86000-00 A01
4.5.1
Disconnecting the Battery Module
1.
Switch the battery circuit breaker(s)
to the
OFF position.
2.
Disconnect the cables
and
from the
power module.
The battery module can be replaced.
The connected equipment is powered by the UPS,
but not protected.
It is also possible to replace battery pack instead of
battery module.
Contact your nearest after sales support service.
CAUTION:
Always replace both battery
packs with new ones.
To remove battery pack:
1.
First, switch the battery circuit breaker(s) to the
OFF position.
See section 2.5 and follow instructions for battery
pack replacement.
4.5.2
Re-connecting the Battery Module
1.
Reconnect the battery cables
and
to
the power module.
2.
Switch the battery circuit breaker(s)
to the
ON position.