Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual
Page 48
![background image](/manuals/123910/48/background.png)
Table 3-3: ON/OFF features.
Display
Factory setting
Options
Comments
Cold start
Disabled
Enabled
Start on battery.
Forced reboot
Enabled
Disabled
Enables automatic restart of
the system even if normal AC
source is restored before the
end of the shutdown sequence.
Automatic restart
Enabled
Disabled
UPS restarts automatically
when normal AC source
is restored.
Sleep mode
Disabled
Enabled
Automatic shutdown on battery
if output load level <10%
Remote Command
Enabled
Disabled
Enables shutdown or restart
orders from software.
Table 3-4: Battery features.
Display
Factory setting
Options
Comments
Battery test
Every week
No test/daily/monthly
Pre-Alarm
20%
0 to 100%
Low battery signal;1% increment
Runtime choice
UPS reads # and type
From 65 to 400 Ah
Requires EX 5/7/11RT CLA if
of battery
using options (see section 1.5.4
modules connected.
“Battery extensions cable kit”)
Battery deep discharge
Enabled
Disabled
If disabled, loss of
protection
MGE UPS SYSTEMS,INC.
warranty.
3.2.2
Accessing personalization through external software
Insert the Solution-Pac CD ROM in your CD drive.
◗
At the first Navigator Screen, select "Installation" and follow the instructions to install Personal
Solution-Pac for Windows.
◗
If nothing appears, launch startup.exe
◗
Then go to "Advanced settings" and "UPS settings".
Please note that the Linux/Unix/MacOS versions of Personal Solution-Pac do not include this feature.
3.2.3
Final startup sequence
Press the <ON> button more than 3 seconds.
◗
After UPS internal test sequence, the green LED
goes on.
CAUTION
During the restart, if the Bypass AC source is out of
tolerance, the UPS will generate an output
calibrated 10 msec output interrupt.
15
EX 5/7/11 RT System
Operation
3 — 4
86-86000-00 A01