Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual
Page 24
![background image](/manuals/123910/24/background.png)
1.5.8
CLA Module (Long backup time charger)
(Part number 86004)
Extended back-up time (up to 8 hours at full load) requires a high power battery cabinet connected to the EX
5/7/11RT via the CLA module.
IMPORTANT
The CLA can not be used to charge the battery module (EXB). It is designed to charge the
customer provided high power battery cabinet.
Figure 1-12: Connection for CLA Module and EX 5/7/11 RT.
Table 5: Battery backup time chart.
Battery Backup Time
Recommended Batteries
EX 5RT
EX 7RT
EX 11RT
2 hours
50 Ah
65 Ah
100 Ah
4 hours
100 Ah
130 Ah
200 Ah
8 hours
200 Ah
200 Ah
400 Ah
Total battery voltage : 240 VDC (20 x 12VDC, one string).
The battery capacity must be set within the UPS (5 Ah increment possible, see UPS Personalization section 3.2.
EX 5/7/11 RT System
Introduction
1 — 12
86-86000-00 A01
EX 5RT /
EX 7RT /
EX 11RT
~
50A
(cable not included)
Typical High Power
Battery Cabinet
(not included)
Utility
AC Source
(cable not included)
(see section 2.10 for cable
connection information)
www
.mge
ups.
com
E X
R T
Tra
nsfor
mer
CLA Module Contents
CLA
Tower Stand Expanders
CLA Documentation
Battery Detection Cable
Battery Power Cable
Stabilizer Bracket
(4 screws included)