Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual
Page 54
4.2
Troubleshooting
◗
If any of LED's
or
is on, there is an operating anomaly or an alarm.
◗
Use "scroll up" or "scroll down" function button to reset the audible alarm.
◗
Troubleshooting not requiring MGE UPS SYSTEMS, INC. after-sales support:
Table 4-2: Troubleshooting not requiring MGE after-sales support.
Symptom
Indication
Correction
LED
is on, and Bypass AC
AC source is not connected
Rewire correctly the normal AC
source is present
to the correct terminals.
source.
the alphanumeric display shows
BAD CONNECTION
REWIRE AC NORMAL
LED
is on,
Load supplied by bypass AC source.
Push the ON button for more than 3
the alphanumeric display shows:
seconds.
LOAD LEVEL
XX kW / XX KVA
LED
is on, and Bypass AC
UPS overload
Check if any device is shorted or failed.
source is present
the alphanumeric display shows:
THERMAL OVERLOAD
1XX%
LED
is on,
Short circuit conditions on output
Check if any device is shorted or
devices.
failed.
the alphanumeric display shows:
CURRENT OVERLOAD
LED
is on,
180° degree phase shift between
Check if bypass source is correctly
bypass and normal AC source.
wired
but the alphanumeric display shows:
(in case of upstream transformer use).
BYPASS REVERSE
REWIRE BYPASS
Audible alarm is on,
Input/Output box not
Check if the Input/Output box
the alphanumeric display shows:
installed correctly.
is correctly installed. See section 2.8.
I/O BOX REMOVED
15
18
17
17
17
18
17
EX 5/7/11 RT System
Maintenance
4 — 2
86-86000-00 A01