Ex 5/7/11 rt system – MGE UPS Systems EX 7RT User Manual
Page 16
1.1
System Electrical Characteristics
Table 3: Power Module Ratings
Part Number
86055
86075
86115
Apparent Power, kVA
5
7
10@ 200/208/250 VAC Output
11@ 220/230/240 VAC Output
Active Power, kW
4
4.9
8@ 200/208/250 VAC Output
7.3@ 220/230/240 VAC Output
Input Current, A
25/24/23/
35/34/32
50/48/50/48/46/40
22/21/20
31/30/28
Input Voltage, VAC
200/208/220/
200/208/220/
200/208/220/230/240/250
230/240/250
230/240/250
Output Current, A
25/24/23/
35/34/32
50/48/50/48/46/40
22/21/20
31/30/28
Output Voltage, VAC
200/208/220/
200/208/220/
200/208/220/230/240/250
230/240/250
230/240/250
CAUTION
Power Module is factory configured at 208Vac, 60 Hz input and output.
Input and Output of the UPS must always be the same.
Table 4: Battery Module Ratings
Part Number
86079
86119
Battery Type
12VDC/7Ah
12VDC/9Ah
Battery Output Voltage
240VDC
240VDC
1.2
Standard Configurations
The EX 5/7/11 RT systems can be set up in tower and rack configurations.
1.2.1
Tower Configuration
Figure 1-1: Tower Configurations with Power Module, Battery Module, and optional Transformer Module.
EX 5/7/11 RT System
Introduction
1 — 4
86-86000-00 A01
www
.mge
ups.
com
www
.mge
ups.
com
E X B
R T
E X
1 1
R T
OFF
ON
BATTERY MODULE
(EXB 5/7/11 RT)
POWER MODULE
(EX 5/7/11 RT)
www
.mgeu
ps.c
om
www
.mge
ups.
com
OFF
ON
BATTERY MODULE
POWER
MODULE
EX 11
RT
EXB
RT
EX RT
Tran
sform
er
EX RT Transformer
www
.mge
ups.
c
om
Standard Configuration
Configuration with Transformer