Installation procedure – Minuteman UPS SNMP-32 Series User Manual

Page 7

background image

7

UPS

Internal SNMP

2. Installation

Procedure


This section will guide you through installing the Internal and the External SNMP-32 card.









Fig. 3-Internal SNMP-32 Card

Internal SNMP-32 card

NOTE:

The SNMP-32 cards are designed to be Hot Swappable, but there is a remote chance that when Hot-Swapping

the SNMP-32 card that the UPS will shutdown. MINUTEMAN recommends following steps 1 through 9 when installing
the SNMP-32 card, but to hot-swap, skip to step number 3 and omit steps 7, 8.
1. Turn off all the equipment that is plugged into the UPS.
2. Turn off the UPS and unplug the UPS’s power cord from the AC wall outlet.
3. Remove the two retaining screws from the option slots cover plate (rear panel of the UPS).
4. Remove the option slot’s cover plate (rear panel of the UPS).
5. Insert the SNMP-32 card into the option slot and re-install the two retaining screws.

6. Connect the Ethernet cable to the Ethernet Port on the SNMP-32 card.
7. Plug the UPS’s power cord into the AC wall outlet and turn the UPS on.
8. Turn on all the equipment that is plugged into the UPS.
9. Now the SNMP-32 is ready to be Setup (see the Setup Procedure).

Fig. 4-External SNMP-32 Card (SNMP-32L Only)

External SNMP-32 card (SNMP-32L Only)

NOTE: The SNMP-32 cards are designed to be Hot Swappable, but there is a remote chance that when Hot-Swapping
the SNMP-32 card that the UPS will shutdown. MINUTEMAN recommends following steps 1 through 11 when installing
the SNMP-32 card, but to hot-swap, skip to step number 3 and omit steps 9, 10.
1. Turn off all the equipment that is plugged into the UPS.
2. Turn off the UPS and unplug the UPS’s power cord from the AC outlet.
3. Plug the power adaptor’s connector into the connector on the external adaptor box, labeled “Input”.
4. Plug the DB9 Male to Female cable into the connector on the external adaptor box, labeled “To UPS”.
5. Plug the other end of the DB9 Male to Female cable into the Serial Port on the UPS (rear panel of the UPS).
6. Plug the power adaptor into one of the Battery Powered outlets of the UPS.
7. Insert the SNMP-32 card into the option slot and install the two retaining screws.
8. Connect the Ethernet cable to the Ethernet Port on the SNMP-32 card.
9. Plug the UPS’s power cord into the AC wall outlet and turn the UPS on.
10. Turn on all the equipment that is plugged into the UPS.
11. Now the SNMP-32 card is ready to be setup (see the Setup Procedure).

UPS

External SNMP

Serial UPS cable

Power
Adapter