beautypg.com

Warning – Monessen Hearth LEXINGTON LX32DV User Manual

Page 18

background image

18

51D0528

LX Series Direct Vent Gas Fireplace

VeNtING INStALLAtIoN

HOT

FP2715
horiz cap w shield

Figure 17 -
Installing Horizontal Vent Cap

Vent Cap

Apply Mastic to
All Four Sides

Deflecting Shield

Wood Screw

FP2715

For vinyl siding, stucco, or wood exterior use vinyl siding
standoffs between vent cap and exterior wall. The vinyl
siding standoff prevents excessive heat from melting the
vinyl siding material. Bolt the vent cap to the standoff. Apply
non-hardening mastic around outside edge of the standoff
instead of the vent cap assembly. Use wood screws pro-
vided to attach the standoff. Figure 18

HOT

Fp2716
vinyl siding standoff

Figure 18 -
Install Vinyl Siding Standoff

Apply Mastic to
All Four Sides

Cut Vinyl Siding Away
to Fit Standoff

Wood Screw

Vent
Cap

Screw

Standoff

Deflecting Shield

FP2716

FP1957
install firestop

Figure 19 -
Connect Vent Cap with Horizontal Vent Pipe

Interior Wall
Surface

Fire Stop
Assembly

Horizontal
Vent Pipe

Screw

Vent Cap
(Horizontal
Termination)

FP1957

hoRIZoNtAL (thRouGh the WALL) teR-
MINAtIoN coNFIGuRAtIoNS

Since it is very important that the venting system main-
tain its balance between the combustion air intake and
the flue gas exhaust, certain limitations as to vent con-
figurations apply and must be strictly adhered to.
The Vent Graph, showing the relationship between vertical
and horizontal side wall venting, will help to determine the
various dimensions allowable. Refer to Page 16
Minimum clearance between vent pipes and combus-
tible materials is 3" on top and 1" from bottom and
sides unless otherwise noted.
When vent termination exits through foundations less than
20" below siding outcrop, the vent pipe must flush up with
the siding.
It is best to locate the fireplace in such a way that minimizes
the number of offsets and horizontal vent length.

W

ARNING

When installing the appliance as a rear
vent unit, the 90°, 45° transition elbow
attached directly to the rear of the unit is
Not INcLuDeD in the following criteria
and calculations, and unless specifically
mentioned should be ignored when
calculating venting layouts.

The horizontal vent run refers to the total length of vent
pipe from the flue collar of the fireplace (or the top of the
Transition Elbow) to the face of the outer wall.

The maximum number of 90° elbows per side wall

installation is three (3). Figure 20

If a 90° elbow is fitted directly on top of the fireplace

flange the maximum horizontal vent run before the ter-
mination or a vertical rise is 36” (914 mm). Figure 21

If a 90° elbow is used in the horizontal vent run (level

height maintained) the horizontal vent length is reduced
by 36" (914 mm). This does not apply if the 90° elbows
are used to increase or redirect a vertical rise. Figure
23

5. Slide fire stop over the vent pipe before connecting the

horizontal run to the vent cap. Figure 19

6. The pipe overlap should be a minimum of 1Z\v". Apply

silicone to the outer pipe connection. Fasten all vent
connections with screws provided.

7. Slide fire stop against the interior wall surface and attach

with screws. Figure 19

This manual is related to the following products: