beautypg.com

Warning – Monessen Hearth LEXINGTON LX32DV User Manual

Page 17

background image

51D0528

17

LX Series Direct Vent Gas Fireplace

VeNtING INStALLAtIoN

ReAR WALL VeNt INStALLAtIoN

When installed as a rear vent unit this appliance may be
vented directly to a termination located on the rear outside
termination behind the appliance

45° elbows may only be attached to rear when used to

direct the flue skyward (to achieve additional rise). Do
not attach 45° elbows to rear of appliance in which the
flue turns either left or right and terminates horizontal.

The maximum horizontal distance between the rear

of the appliance and the outside face of the outside
termination is 20" (508 m). Figure 15

DVR584-600
Rear vent no elbows
2/99 djt

Figure 14 -
Rear Vent Application,
Maximum Horizontal Distance

20"(508 mm)

Maximum

DVR584

1. Locate and cut the vent opening in the wall. For com-

bustible walls first frame in opening. Figure 15

combustible Walls: Cut a 11Z\x"H x 9Z\x" W (292 x 24

mm) hole through the exterior wall and frame as shown.
Figure 15

Noncombustible Walls: Hole opening should be 7Z\x"

(190 mm) in diameter.

VO584-100
Vent Opening
2/99 djt

9Z\x"

(241 mm)

11Z\x"

(292 mm)

Vent opening for combustible Walls

Fireplace Hearth

Framing Detail

Vent opening for Noncombustible Wall

7Z\x"

(190 mm)

Fireplace Hearth

VO584-100

Figure 15 -
Locate Vent Opening on Wall

FP1953
rigid pipe

Figure 16 -
Rigid Vent Pipe Connections

Note: horizontal runs of
vent must be supported
every 3' (914 mm). use wall
straps for this purpose.

Female
Locking Lugs

Male Slots

FP1953

2. Rigid vent pipes and fittings have special twist-lock

connections. Assemble the desired combination of pipe
and elbows to the appliance adaptor with pipe seams
oriented towards the wall or floor.

Twist-lock Procedure: The female ends of the pipes

and fittings have three locking lugs (indentations).
These lugs will slide straight into matching slots on
the male end of adjacent pipes and fittings. Push the
pipe sections together and twist one section clockwise
approximately one-quarter turn until the sections are
fully locked. Figure 16

3. Attach vent pipe assembly to the fireplace. Set fireplace

in front of its permanent location to insure minimum
clearances. Mark the wall for a 11Z\x"H x 9Z\x"W (292 x 24
mm) rectangle hole (for noncombustible material such
as masonry block or concrete, a 7Z\x" [190 mm] diameter
hole is acceptable). Figure 15. The center of the hole
should line up with the center line of the horizontal rigid
vent pipe end. Be sure to allow for minimum rise. Cut
a 11Z\x" x 9Z\x" (292 X 241 mm) rectangle hole through
combustible exterior wall (7Z\x" [190 mm] diameter hole
if noncombustible). Frame as necessary. Allow 1/4"
minimum rise per foot. Figure 15

4. Apply a bead of non-hardening mastic around the

outside edge of vent cap. Position the vent cap in the
center of hole on the exterior wall with the word “UP”
on the vent cap facing up. Insure proper clearance of
1" to combustibles is maintained. Attach the vent cap
with four wood screws supplied. Figure 17

Note: Replace the wood screws with appropriate fasteners
for stucco, brick, concrete, or other types of siding.

W

ARNING

Do not recess vent termination into any
wall. this will cause a fire hazard.

This manual is related to the following products: