9. Charge the system with the proper refrigerant to
the nameplate charge.
10. Operate the ice machine for one hour. Then,
check the pressure drop across the suction line
filter-drier.
a) If the pressure drop is less than 2 psig, the
filter-drier should be adequate for complete
cleanup.
b) If the pressure drop exceeds 2 psig, change
the suction line filter-drier and the liquid line
drier. Repeat until the pressure drop is
acceptable.
11. Operate the ice machine for 48-72 hours. Replace
the suction line and liquid line drier if necessary.
12. Follow normal evacuation procedures.
See also other documents in the category Manitowoc Ice Freezers:
- RF0300 (1 page)
- K00343 (1 page)
- AUCS-SI K00363 (1 page)
- FLAKE/CHIPLET QF2300 (150 pages)
- SD0672C (3 pages)
- K00055 (1 page)
- Q-0210 (1 page)
- K00372 (4 pages)
- QC0700 (1 page)
- RF1200 (2 pages)
- 7600143 (1 page)
- K00022 (1 page)
- F-STYLE OR NON MANITOWOC BIN 7601193 (3 pages)
- 7622333 (1 page)
- S (60 pages)
- K00114 (1 page)
- S0850M (38 pages)
- K00117 (1 page)
- K00368 (1 page)
- K00127 (1 page)
- 7626813 (1 page)
- S1400M (38 pages)
- S600M (40 pages)
- QM30 Series (28 pages)
- K00119 (1 page)
- K00142 (2 pages)
- E-0600 (2 pages)
- BR-0490N (2 pages)
- TIMER GSI 200 (2 pages)
- K00135 (1 page)
- 7626213 (4 pages)
- K00047 (1 page)
- Q (52 pages)
- MFD-50 (1 page)
- JR/QR0490N (1 page)
- BULKHEAD Q-1400 (2 pages)
- KEY CARD KIT K00152 (1 page)
- Q-1300 (3 pages)
- 7622073 (1 page)
- MAC 6 K059 (2 pages)
- K00349 (3 pages)
- SN20 (1 page)
- LEFT SIDE SPLASH SHIELD J-0320 (1 page)
- Q300 (45 pages)
- K00066 (1 page)