SUCTION PRESSURE HIGH CHECKLIST

Problem

• Cause

Improper Installation

Refer to “Installation/Visual Inspection Checklist”

Discharge Pressure

Discharge pressure is too high, and is affecting

suction pressure, refer to “Freeze Cycle Discharge

Pressure High Checklist”

Improper Refrigerant Charge

• Overcharged

Wrong type of refrigerant

Non Condensable in system

Other

Non-Manitowoc components in system

Hot gas valve leaking

• Defective

compressor

Water inlet valve leaking

SUCTION PRESSURE LOW CHECKLIST

Problem

• Cause

Improper Installation

Refer to “Installation/Visual Inspection Checklist”

Discharge Pressure

Discharge pressure is too low, and is affecting

suction pressure, refer to “Freeze Cycle Discharge

Pressure Low Checklist”

Improper Refrigerant Charge

• Undercharged

Wrong type of refrigerant

Other

Non-Manitowoc components in system

Improper water supply over evaporator refer to

“Water System Checklist”

Loss of heat transfer from tubing on back side of

evaporator

Restricted/plugged liquid line drier

Restricted/plugged tubing in suction side of

refrigeration system

NOTE: Do not limit your diagnosis to only the items

listed in the checklists.