SUCTION PRESSURE HIGH CHECKLIST
Problem
• Cause
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
Discharge Pressure
•
Discharge pressure is too high, and is affecting
suction pressure, refer to “Freeze Cycle Discharge
Pressure High Checklist”
Improper Refrigerant Charge
• Overcharged
•
Wrong type of refrigerant
•
Non Condensable in system
Other
•
Non-Manitowoc components in system
•
Hot gas valve leaking
• Defective
compressor
•
Water inlet valve leaking
SUCTION PRESSURE LOW CHECKLIST
Problem
• Cause
Improper Installation
•
Refer to “Installation/Visual Inspection Checklist”
Discharge Pressure
•
Discharge pressure is too low, and is affecting
suction pressure, refer to “Freeze Cycle Discharge
Pressure Low Checklist”
Improper Refrigerant Charge
• Undercharged
•
Wrong type of refrigerant
Other
•
Non-Manitowoc components in system
•
Improper water supply over evaporator refer to
“Water System Checklist”
•
Loss of heat transfer from tubing on back side of
evaporator
•
Restricted/plugged liquid line drier
•
Restricted/plugged tubing in suction side of
refrigeration system
NOTE: Do not limit your diagnosis to only the items
listed in the checklists.