Manitowoc Ice CM MODEL STH003 User Manual
Page 73
73
Charging Procedures
IMPORTANT
The charge is critical on all Manitowoc ice
machines. Use a scale to ensure the proper
charge is installed. A quick disconnect is required
for the high side connection
1. Be sure the toggle switch is in the OFF position.
2. Close the vacuum pump valve and the low side
manifold gauge valve.
3. Open the high side manifold gauge valve.
4. Using a digital scale add the proper refrigerant
charge (shown on nameplate) through the high
side.
5. Close/isolate the refrigerant cylinder.
6. Let the system “settle” for 2 to 3 minutes.
7. Place the toggle switch in the ICE position.
8. Close the high side on the manifold gauge set.
NOTE: Manifold gauges must be removed properly to
ensure that no refrigerant contamination or loss occurs.
A quick disconnect is required for the high side
connection.
- RF0300 (1 page)
- K00343 (1 page)
- AUCS-SI K00363 (1 page)
- FLAKE/CHIPLET QF2300 (150 pages)
- SD0672C (3 pages)
- K00055 (1 page)
- Q-0210 (1 page)
- K00372 (4 pages)
- QC0700 (1 page)
- RF1200 (2 pages)
- 7600143 (1 page)
- K00022 (1 page)
- F-STYLE OR NON MANITOWOC BIN 7601193 (3 pages)
- 7622333 (1 page)
- S (60 pages)
- K00114 (1 page)
- S0850M (38 pages)
- K00117 (1 page)
- K00368 (1 page)
- K00127 (1 page)
- 7626813 (1 page)
- S1400M (38 pages)
- S600M (40 pages)
- QM30 Series (28 pages)
- K00119 (1 page)
- K00142 (2 pages)
- E-0600 (2 pages)
- BR-0490N (2 pages)
- TIMER GSI 200 (2 pages)
- K00135 (1 page)
- 7626213 (4 pages)
- K00047 (1 page)
- Q (52 pages)
- MFD-50 (1 page)
- JR/QR0490N (1 page)
- BULKHEAD Q-1400 (2 pages)
- KEY CARD KIT K00152 (1 page)
- Q-1300 (3 pages)
- 7622073 (1 page)
- MAC 6 K059 (2 pages)
- K00349 (3 pages)
- SN20 (1 page)
- LEFT SIDE SPLASH SHIELD J-0320 (1 page)
- Q300 (45 pages)
- K00066 (1 page)