Figure 2.12 — Spark Arrestor Installation

40 [1.58"]

5.5 [7/32"] DRILL
BOTTOM SIDE ONLY

27.4 [1.08"] I.D.

2.5.2 exhaust systeM saFety

• Maintain a clearance of at least 3 inches (76 mm)

between exhaust system parts and any combus-

tible material (such as wood, felt, cotton, organic

fibers or other like material). If the 3-inch (76 mm)

clearance cannot be maintained, locate, insulate or

shield the exhaust part(s) so that the temperature

of any combustible material is not raised more

than 117° F (65° C) above the ambient air tempera-

ture.

• Extend the exhaust system at least 1 inch (25 mm)

past the outer edge of the vehicle. Do not terminate

the exhaust system under the vehicle.

• Terminate the exhaust tailpipe such that exhaust

gases will not be drawn back into the generator

compartment and recirculated.

• If there is any possibility of the tailpipe or muffler

being damaged, protect these damage-prone areas

by means of a protective device (such as a skid

bar).

• Install the generator exhaust system according to

safe automotive practices.

• Use enough exhaust system hangers to prevent any

part of the system from being dislocated.

• Use exhaust system parts recommended by the

manufacturer. Using unapproved exhaust mufflers

and exhaust system parts is the responsibility of

the person(s) installing such unauthorized parts.

• Do not terminate the exhaust system under any

opening, window or vent that can be opened or is

not permanently sealed from the vehicle interior.

• Exhaust piping must be large enough to prevent

excessive back pressure on the generator engine.

• Never tee the generator engine exhaust pipe into

the vehicle engine exhaust piping. This causes

excessive back pressure on the generator engine.

Also, water from one engine can damage the other

engine.

• Plan exhaust system installation carefully. Comply

with all applicable codes, standards and regula-

tions.

2.6 electrIcal connectIons

Be sure to read Section 1.6.
The following general rules apply to electrical connec-

tions in a recreational vehicle:
• Qualified electricians who are familiar with appli-

cable codes, standards and regulations should

install electrical wiring.

• The wiring should comply with codes, standards

and regulations. The National Electrical Code

(NFPA 70), and state and local codes apply.

• Switches and circuit breakers should be of a type

approved for use in recreational vehicles and must

be mounted and installed to prevent damage from

road shock.

• Wiring must be of adequate size, have approved

insulative qualities and be properly supported.

• Conduit and wire openings into the generator com-

partment (if used) must be vapor-sealed to prevent

entry of flammable, explosive or poisonous gases

into the vehicle.

2.6.1 electrIcal junctIon box

Install an approved, square electrical junction box

with a blank cover on the interior or exterior wall of

the area planed for installation of the generator (NOT

on the generator). Route the generator's AC output

leads into this junction box through approved flex-

ible conduit. This is the point of first termination for

generator AC output leads.

2.6.2 wIrIng

• Wiring should be of stranded copper to reduce the

chance that vibration may cause breakage.

• Wire gauge size should be large enough to handle at

least 115 percent of the installed generator's rated

maximum current.

• Neutral conductors must be the same size as other

leg wires.

• Route power supply conductors from generator AC

output leads (white), (black) and the green ground

wire through approved flexible conduit to the elec-

trical junction box on the compartment wall.

If flexible metal conduit is used between the gen-

erator and the compartment junction box, the con-

duit end that terminates the compartment junction

box must be vapor-sealed. Flexible metal conduit

is NOT vapor tight along its entire length.

• From the junction box, route power supply wires

through approved conduit to either (a) double-pole,

double-throw transfer switch, or (b) approved iso-

lation receptacle. Connecting to a transfer switch

or isolation receptacle must prevent vehicle electri-

cal circuits from being connected to two different

power supplies at the same time (such as genera-

tor and dockside power).

section 2 – Installation

recreational vehicle generator