Guardian Technologies QUIETPACT 40LP 004701-0 User Manual

Page 27

background image

• Use a length of approved flexible fuel hose between

the gaseous fuel solenoid valve and rigid gas pip-

ing. The flexible line should be at least 6 inches

longer than necessary.

2.4.3 vapor wIthdrawal

LP gas is stored in pressure tanks as a liquid. The

gas systems used with these generators were designed

only for vapor withdrawal type systems. Vapor with-

drawal systems use the gas vapors that form above

the liquid fuel in the tank. Do NOT attempt to use the

generator with any liquid withdrawal type system.

2.4.4 prIMary regulator

Gas pressure delivered to the solenoid valve must be

properly regulated by means of a primary gas regu-

lator. Mount the primary regulator at the gas tank

outlet or in the supply line from the gas tank. The

following rules apply:
• For best results, the primary regulator supplies

gaseous fuel to the secondary regulator at 11 inch-

es water column. Do NOT exceed 14 inches water

column.

• The installer must be sure the primary regulator is

rated at sufficient gas flow to operate the generator

plus all other gas appliances in the circuit.

NOTE:

Recommended MINIMuM gas flow rate for all air-

cooled generators is 40 cubic feet per hour.
If an existing primary gas regulator does not have

a sufficient flow capacity for the generator and

other gas appliances in the circuit, (a) install a

primary regulator with adequate flow rate, or (b)

install a separate regulator only and rated at least

40 cubic feet per hour. The inlet side of any pri-

mary regulator that supplies the generator must

connect directly to a gas pressure tank. Do NOT

tee the generator line into a gas circuit feeding

other areas.

2.4.5 gaseous carburetIon

LP gas vapors should be supplied to the secondary

regulator inlet at about 11 inches water column (posi-

tive pressure). The engine pistons draw air in dur-

ing the intake stroke (Figure 2.10). This air passes

through a carburetor venturi, which creates a low

pressure that is proportional to the quantity of air

being pumped. The low pressure from the carburetor

venturi acts on the regulator diaphragm to pull the

diaphragm toward the source of low pressure. A lever

attached to the diaphragm opens a valve to permit

gas glow through the carburetor.

Figure 2.10 – LP Gas Carburetion Diagram

The greater the airflow through the carburetor ven-

turi, the lower the pressure at the venturi throat. The

lower the pressure at the venturi throat, the greater

the diaphragm movement, and the greater the move-

ment of the regulator valve. The more the regulator

valve opens, the greater the gas flow that is propor-

tional to airflow through the generator.
The following facts about the secondary regulator

must be emphasized:
• The regulator must be sensitive to venturi throat

pressure changes throughout the operating range.

• The regulator must be properly adjusted so it will

stop the flow of gas when the engine is not running

(no air flow through the carburetor).

• The slightest airflow (and vacuum in the venturi

throat) should move the regulator valve off its seat

and permit gas to flow.

2.4.6 Fuel supply lInes

• LP gas lines must be accessible, but protected

against possible damage.

• Do NOT connect electrical wiring to any LP gas fuel

line or run wiring alongside the lines.

• Route gas lines away from hot engine exhausts.
• Retain gas lines with metal clamps that do not have

sharp edges.

• Install an approved length of flexible hose between

the gaseous fuel solenoid valve and rigid fuel

supply lines. The flexible line must be nonmetal-

lic, nonorganic and nonconductive. It must be

approved for use with LP gas.

2.4.7 excess Flow valve

LP gas tanks should have an excess flow valve,

according to NFPA 501C, Paragraph 3-4.4. This

valve and the gas lines must be carefully sized so the

valve will close when a fuel line is severed or broken.

Consult the Natural-LP Gas Association for informa-

tion and limitations of excess flow valves.
Manual shutoff valves on the supply tank and else-

where in the system must be fully open when oper-

ating the generator. The excess flow valve functions

properly only if all valves are fully open.

section 2 – Installation

recreational vehicle generator