GE SG SERIES 20 User Manual
Page 75
g
GE
OPM_SGS_USM_10K_40K_0US_V010.doc
75/88 Operating
Manual
SG Series 10, 20, 30 & 40 kVA
7.4.7 Restore to normal operation after “total off”
View of the panel after pressing the button “total off”.
•
All Contacts are open;
•
Rectifier, Inverter and Static-Switch shutdown.
First operated unit
All other units of the system
1. Reset “total off” by pressing and holding the “total off” button and then the
“inverter on” ( I ) key, on any of the Units simultaneously, until Load is supplied
from Bypass and the Rectifiers start.
•
System output connects to Bypass Utility.
•
Rectifiers start with blinking LED.
•
At the end of Soft-start the LED’s remains lit.
•
The LCD screen
on all Units
shows: “LOAD ON BYPASS”.
First operated unit
All other units of the system
2. Connect the Battery to all Units by closing the external Battery Switch(es) or
Fuses.
Continue
►