GE SG SERIES 20 User Manual
Page 34
g
GE
OPM_SGS_USM_10K_40K_0US_V010.doc
34/88 Operating
Manual
SG Series 10, 20, 30 & 40 kVA
5. Printer
Set-up
The UPS is capable of communicating to a serial printer, to printout disparate information.
Please be sure to have a serial printer, that is a printer with a serial RS232 interface.
This is the only printer-interface supported by the UPS.
PRINTER SETUP
Baud=2400 Parity=O
Bits=8 Handshake=XON
Print All = N
metering
alarms
parameters
+
–
ok
Baud Rate
This parameter controls the baud rate used for data transmission.
Although different values can be selected, you must select 2400 Baud,
which is the only valid parameter.
Parity
This parameter controls the parity used for data transmission.
Odd (O) even (E) and “no parity” (X) can be selected.
Nevertheless the only valid value is NO PARITY (X).
Bits
This parameter controls the length of the data word on the serial line during
data transmission 7 or 8 bits are offered as choice.
Please
select
8 bits, as this is the only valid value.
Handshake
This parameter is used to determine the communication protocol used when
printing.
Valid
values
are “XON” standing for the XON/XOFF protocol or “NO”
standing for any protocol.
Print All This
parameter
Y/N is used to print all the available information in the
sequence metering, alarms, user and service parameters.
Please configure your printer with the following parameters: 2400/8/N (2400
bits/sec, 8 bits, no parity).
6. Printer
commands
PRINTER CO M M ANDS
Print M easures
= N
Print Alarm s
= N
Print Param eters = N
m etering
alarm s
param eters
+
–
ok
Print Measures This
Y/N parameter is used to print only the measurement data.
Print Alarms This
Y/N parameter is used to print only the sequence of all
Alarms/Events.
Print Parameters This
Y/N parameter is used to print only the list of User and Service
Parameters
After each printing command the corresponding parameter will be set again
to N.