GE SG SERIES 20 User Manual
Page 73
g
GE
OPM_SGS_USM_10K_40K_0US_V010.doc
73/88 Operating
Manual
SG Series 10, 20, 30 & 40 kVA
7.4.6 Parallel system shutdown (No Load supply)
The Load must be disconnected.
Initial status: Load supplied from all Inverters.
First operated unit
All other units of the system
1. Press “total off” button on any one on the units.
•
Load is disconnected from UPS.
•
Rectifier and Inverter are shut down and all output and input contactors will be
opened.
•
LED’s, Rectifier, Inverter and Load are OFF.
First operated unit
All other units of the system
2. Open Q1 (Pos. O) on all Units.
First operated unit
All other units of the system
Continue
►
This manual is related to the following products: