GE SG SERIES 20 User Manual
Page 38
g
GE
OPM_SGS_USM_10K_40K_0US_V010.doc
38/88 Operating
Manual
SG Series 10, 20, 30 & 40 kVA
Code
Alarms
Meaning
4697
BATTERY
OVERTEMPERATURE
Detection of Battery over temperature condition.
Can be deactivated by Service.
4698
BATTERY POWER
INSUFFICIENT
In case of Utility Failure, with the actual Load, the run time
would be below stop operation time (default 3 minutes).
4700
DC LOW
Battery voltage is at the lowest limit.
Will stay Off inverter until the battery voltage reaches the
value in parameter.
4900
LOAD LOCKED
ON INVERTER
The Load is locked on Inverter after 3 Load transfers within 30
seconds.
After time out (default 30 sec.) Bypass will be free.
4955 OVERTEMPERATURE
An over-temperature condition has been detected on Inverter.
Elapsed “stop operation” time, Inverter shutdown.
With Utility OK, Load is transferred on Utility.
4998
LOAD OFF DUE TO
EXTENT. OVERLOAD
Load Off after time-out of “stop operation” for overload on
Inverter or Bypass (time depending on the % of overload).
4999
LOAD OFF DUE
TO UBATT. OR TEMP.
Load Off after time-out of “stop operation” with missing Utility
due to Battery low voltage or over-temperature condition.