GE SG SERIES 20 User Manual
Page 45
g
GE
OPM_SGS_USM_10K_40K_0US_V010.doc
45/88 Operating
Manual
SG Series 10, 20, 30 & 40 kVA
7.1.3 From Manual Bypass (Q2) to normal function On-line
Initial status:
Load supplied from Manual Bypass.
1. Close Q1 (Pos. I).
•
Bypass connects to Load.
LED Load on Bypass lights up.
•
Rectifier starts automatically and
LED in Rectifier symbol and LED
Battery charge light up.
2. Open Q2 (Pos. O).
•
LED Manual Bypass turns OFF.
3. Connect the Battery to the UPS by closing the Battery Switch or Fuses, in
case of External Battery .
4. Press “inverter on” ( I ) key.
•
Soft-start of Inverter, indicated with
blinking LED.
•
At the end of Soft-start the LED
remains lit.
•
Automatic transfer from Bypass to
Inverter.
•
UPS output LED indicates Load on
Inverter.
The LCD must display on the main screen the status “LOAD ON INVERTER”.
End of procedure