MAINTENANCE

- 31 -

fault finding

12.1 Preliminary fault finding

The following checks should be performed before proceeding

onto specific diagnostics:

• Check the external electrical supply to the boiler is on and

a supply of 230V is present at the ‘L’ and ‘N’ terminals on

the installer interface, refer to section 10.4 for access and

diagram 12.4.

• Check the electrical installation and appliance, carry

out tests for earth continuity, polarity, short circuit and

resistance to earth, using a suitable multimeter.

an aid to test

Remove the front casing panel, see diagram 11.2 and the

control panel securing screw, see diagram 12.1 then lower

into service the position.

Remove the rear panel by prising the retaining clips, see

diagram 12.1.

Carry out the tests at connector plug X17, see diagram 12.2.

Check chassis earth at a bare metal point on the boiler.

• Check that there is a gas supply to the boiler and the gas

service isolation valve is turned on, see diagram 10.1.

• Check pressure at the gas service isolation valve, refer to

section 10.5.

• Check that the heating system pressure indicates at least

1mb, if not, fill and vent the system as described in section

10.2.

• Check that all external controls are on.

• Check the functional flow diagram, 12.5.

12.2 fault Codes

Fault codes take priority over all other display functions in the

event of a fault occurring, refer to diagram 12.6.

If multiple faults occur the codes will be displayed for approx.

2 seconds, alternatively.

12.3 fault Memory

The Fault memory stores details of the ten most recent faults.

To access this menu, refer to diagram 12.3:

a) Press and hold ‘MODE’ for 5 seconds.

b) When the display shows a flashing ‘0’ press ‘MODE’

button.

c) Press a ‘+’ button to scroll back through the fault memory

(Position 1 is most recent), see fault memory display.

To exit this menu, press the ‘MODE’ button.

12.4 Diagnostic Menu

The Diagnostic Menu provides the ability to view and

change certain parameters. See diagram 12.7 for available

parameters.

12.5 Status Codes

The status codes provide information about the current

operating condition of the boiler and can be accessed through

the diagnostic display, refer to diagram 12.8.

13738

Diagram 12.1

REAR

PANEL

CHASSIS FRONT

CONTROL BOX

SERVICE POSITION

SECURING

SCREW

CLIPS

13845

Diagram 12.2

13452

Diagram 12.3