INSTALLATION

- 12 -

4.2 flue configuration description

4.2.1

Horizontal concentric flue Ø 60/100 mm

or Ø 80/125 mm (C13 type installation)

a

If the terminal is at less than 1.80 m from the

ground, you must install a terminal protection

kit.

Ø 60/100 mm

L

63

1

Key

1 Gasket (fitted)

Ø 80/125 mm

L

1

Key

1 Gasket (fitted)

Type

Max length

Ø 60/100

10 m

Ø 80/125

25 m

Each time an additional 90° bend is necessary (or 2 at 45°),

the length (L) must be reduced by 1 m.

4.2.2

Vertical concentric flue Ø 60/100 mm

or Ø 80/125 mm (C33 type installation)

a

If the terminal is at less than 1.80 m from the

ground, you must install a terminal protection

kit.

L

Type

Max length (l)

Ø 60/100

10 m

Ø 80/125

25 m

Each time an additional 90° bend is necessary (or 2 at 45°),

the length (L) must be reduced by 1 m.